L4188A,B; L4189A,B; L6188A-C; L6189A-C AQUASTAT® CONTROLLERS

7

68-0061—1

Fig. 9. High Limit and Low Limit/Circulator Application in

an Oil-Fired Hydronic System with domestic hot water.

Fig. 10. High Limit and Separate Low Limit and Circulator

Application in an Oil-Fired Hydronic System with

Domestic Hot Water.

OPERATION

As the liquid filing the sensing bulb and capillary expands and

contracts, it moves a diaphragm. Movement of the diaphragm

is transferred by a lever to the snap-acting switch in the

controller.

High or Low Limit Action (L4188, L4189)

The normally closed C-1 contacts open on temperature rise to

the set point, shutting off power to the controlled circuit. On

auto recycle models, the switch closes C-1 after the

temperature falls past the set point and through the differential

(See Fig. 11).

Low Limit/Circulator Action (L6188, L6189)

The low limit is connected to the normally closed C-1 contacts,

and the circulator to the normally open C-2 contacts. As long

as the temperature at the sensing bulb is above set point, the

circulator runs. If sensing bulb temperature falls past the set

point and through the differential, the switch breaks C-2 to turn

off the circulator, and makes C-1 to turn on the burner. When

the temperature rises to the set point, C-2 makes to turn on the

circulator, and C-1 breaks to turn off the burner.

On manual reset models, the reset button must be pushed

before contacts C-1 will close (See Fig. 11).

Fig. 11. Aquastat Controller Switch Action on Temperature

Change.

ADJUSTMENTS

To Set Temperature

KNOB MODELS

Line up the desired temperature setting with the temperature

setting indicator behind the knob.

SCREWDRIVER SLOT MODELS

Line up the pointer on the shaft with the desired temperature

setting printed on the case.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

1

L4188 OR L4189 USED AS HIGH LIMIT.

2

24V THERMOSTAT

PROTECTORELAY

CONTROL

BLACK

T

CIRCULATOR

L1

(HOT)

L2

2

3

HIGH LIMIT

BURNER MOTOR

IGNITION

ORANGE

WHITE

T

LOW LIMIT

RELAY CENTER

CIRCULATOR

MOTOR

R

G

C

1

2

L6188 OR L6189 USED AS LOW LIMIT/CIRCULATOR CONTROLLER.

3

M25422

PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS

REQUIRED.

1

24V

THERMOSTAT

PROTECTORELAY

CONTROL

BLACK

T

CIRCULATOR

L1

(HOT)

L2

BURNER

IGNITION

ORANGE

WHITE

T

T

T

X

X

4

1

2

L4188.9

CIRCULATOR

L4188.9

LOW LIMIT

L4188.9

HIGH LIMIT

SWITCHING RELAY

RA832A

LINE VOLTAGE

LOW VOLTAGE

1

M25423

SET POINT

DIFFERENTIAL

TEMPERATURE

SETTING

SCALE

L4188.9

HIGH OR LOW

LIMIT

L6188.9

LOW LIMIT/

CIRCULATOR

SET POINT

SET POINT
LESS

DIFFER-

ENTIAL

BREAKS

MAKES

AUTO

RECYCLE

C-1 BREAKS

C-2 MAKES

C-1 MAKES

C-2 BREAKS

MANUAL

RESET

MAKES C-1

C 1

C 1

2

C 1

C 1

2

2

C

1

220 F

100 F

M25424