Hubbell Electric Heater Company EMV User Manual

Page 21

Advertising
background image

MIXING VALVE

1. Disconnect power from unit.
2. Shut off incoming water supply.
3. Lift test lever on relief valve to relieve pressure in tank.
4. Drain tank.
5. Disconnect unions on both sides of the mixing valve.
6. Remove mixing valve.
7. Replace mixing valve.
8. Fill system in accordance with procedures on page 9.


Acorn Nut Cap

Hot Water Inlet Cold Water Inlet






Union Union









Tepid Water Outlet

RE-CALIBRATE MIXING VALVE

1. Remove small domed acorn nut cap on top of the diaphragm actuator.
2. Without turning the adjustment screw, loosen the locknut securing the adjustment screw.
3. Turn on the water at the shower or eye/face wash and monitor the water temperature during

calibration.

4. Using a 1/8” allen wrench, turn the adjustment screw counter-clockwise to raise the outlet water

temperature or clockwise to lower the outlet water temperature.

5. Start by turning the adjustment screw only one full turn, then observe the water temperature and the

shower or eye/face wash fixture.

6. If needed, turn the adjustment screw an additional ½ turn at a time until the desired water temperature

is reached.

7. Turn off the water at the shower or eye/face wash fixture.
8. Lock the adjustment screw with the locknut.
9. Replace the domed acorn nut cap over the adjustment screw.
10. Re-check the outlet water temperature as described in Section III, Scheduled Maintenance and

Operation, Monthly Inspection – Mixing Valve.

21

Advertising