Preventive maintenance, Replacement parts – Heatcraft Refrigeration Products H-IM-FL1A User Manual

Page 15

Advertising
background image

15

Preventive Maintenance

Air Cooled Condensing Units

Quarterly

1) Visually inspect unit
• Look for signs of oil stains on interconnection piping and

condenser coil. Pay close attention to areas around solder

joints, building penetrations and pipe clamps. Check any

suspect areas with an electronic leak detector. Repair any

leaks found and add refrigerant as needed.
• Check condition of moisture indicator/sightglass in the

sight glass if so equipped. Replace liquid line drier if there

is indication of slight presence of moisture. Replace

refrigerant, oil and drier if moisture concentration is

indicated to be high.
• Check moisture indicator/sightglass for flash gas. If found

check entire system for refrigerant leaks and add refrigerant

as needed after repairing any leaks.

Check compressor sightglass (if equipped) for proper oil level.

• Check condition of condenser. Look for accumulation of dirt

and debris (clean as required).
• Check for unusual noise or vibration. Take corrective action

as required.
• Inspect wiring for signs of wear or discoloration and repair

if needed.
• Check and tighten all flare connections.

Semi-Annually

2) Repeat all quarterly inspection items.

3) Clean condenser coil and blades
• Periodic cleaning can be accomplished by using a brush,

pressurized water and a commercially available foam coil

cleaner. If foam cleaner is used, it should not be an acid

based cleaner. Follow label directions for appropriate use.
• Rinse until no residue remains.
4) Check operation of condenser fans
• Check that each fan rotates freely and quietly. Replace any

fan motor that does not rotate smoothly or makes excessive

noise.
• Check all fan blade set screws and tighten as required.
• Check all fan blades for signs of cracks, wear or stress.

Pay close attention to the hub and spider. Replace blades

as required.
• Verify that all motors are mounted securely.
• Lubricate motors if applicable. Do not lubricate permanently

sealed, ball bearing motors.
5) Inspect electrical wiring and components
• Verify that all electrical and ground connections are secure,

tighten as required.

• Check condition of compressor and heater contactors. Look

for discoloration and pitting. Replace as required.
• Check operation and calibration of all timers, relays

pressure controls and safety controls.

• Clean electrical cabinet. Look for signs of moisture, dirt,

debris, insects and wildlife. Take corrective action as

required.
• Verify operation of crankcase heater by measuring amp

draw.
6) Check refrigeration cycle

• Check suction, discharge and net oil pressure readings. If

abnormal take appropriate action.
• Check operation of demand cooling, liquid injection or

unloaders if so equipped.
• Check pressure drop across all filters and driers. Replace

as required.
• Verify that superheat at the compressor conforms to

specification. (30°F to 45°F)
• Check pressure and safety control settings and verify

proper operation.

Annually

7) In addition to quarterly and semiannual maintenance checks,

submit an oil sample for analysis

• Look for high concentrations of acid or moisture. Change oil

and driers until test results read normal.
• Investigate source of high metal concentrations, which

normally are due to abnormal bearing wear. Look for liquid

refrigerant in the crankcase, low oil pressure or low super-

heat as a possible source.

Replacement Parts

Whenever possible, replacement parts are to be obtained

from a local wholesaler authorized to sell one of Heatcraft

Refrigeration Productsʼ brands. Replacement parts which

are covered under the terms of the warranty statement

on page 2 of this manual, will be reimbursed for total part

cost only. The original invoice from the parts supplier

must accompany all warranty claims for replacement part

reimbursement. Heatcraft Refrigeration Products reserves

the right to adjust the compensation amount paid on any

parts submitted for warranty reimbursement when a parts

supplierʼ s original invoice is not provided with a claim.

You may obtain information regarding local authorized

wholesalers by calling the Heatcraft Refrigeration Products

Replacement Parts Center at 1-800-686-7278 between the

hours of 7:30 AM to 4:30 PM Central Time.

Advertising