Condensing unit accessories, Suction filters, driers, sight glasses – Heatcraft Refrigeration Products H-IM-FL1A User Manual

Page 5

Advertising
background image

5

Suction Filters, Driers, Sight Glasses

There are two types of suction and liquid filter/driers used

on Heatcraft Refrigeration Products units. Replaceable core

and/or sealed units are used, dependent upon the option

package ordered.
Suction filters, regardless of type, are always installed

upstream of the compressor suction service valve, and

any accumulators or other options that may be installed.

Suction filters are equipped with “Schrader” type access

valves to allow field measurement of pressure drop across

the device. This allows plugged filters and elements to be

identified very quickly and easily so they can be replaced

when the pressure drop is excessive. Refer to the specific

manufacturersʼ recommendation on servicing these units by

make and model.
Liquid filter/driers, regardless of type, are always installed

downstream of the receiver outlet service valve, and up-

Condensing Unit Accessories

stream of the liquid line solenoid valve (if supplied). Liquid line

driers may or may not have an access valve, dependent on the

size and application. The basic servicing of these units is similar

to suction filters. Liquid line driers should be replaced whenever

there is evidence of excessive pressure drop across the filter,

or the system becomes contaminated due to system leaks,

compressor burnouts, acid formation, or moisture accumulation

as indicated by the liquid line sight glass.
The sight glass is installed in the main liquid line assembly,

downstream from the receiver outlet service valve, and

immediately after the liquid line drier. The sight glass is

designed to give a visual indication of moisture content in the

system. Generally, it requires no field service. However, in

cases of extreme acid formation in a system after a compressor

burnout, the acid may damage the sensing element or etch the

glass. This would require that the sight glass be replaced, along

with the liquid line drier after any compressor motor burnout.

CAUTION: Fans closest to the headers should not be

cycled on standard temperature or pressure

controls. Dramatic temperature and pressure

changes at the headers as a result of fan action

can result in possible tube failure. Fan motors are

designed for continuous duty operation.

Fan cycling controls should be adjusted to maintain a minimum

of (5) minutes on and (5) minutes off. Short cycling of fans may

result in a premature failure of motor and/or fan blade.

Compressors operating below +10°F SST must have air flowing

over the compressor at all times when the compressor is

running.

Design

Thermostat Settings

Models

T.D.

T1

T2

T3

30

60

2-fan units:

25

65

20

70

4-fan units:

15

75

30

60

40

3-fan units:

25

65

55

20

70

60

6-fan units:

15

75

65

30

60

50

30

8-fan units:

25

65

55

40

20

70

65

50

15

75

70

60

NOTE: Cycle pairs of fans on double wide units.

Table 2. Thermostat Settings

Table 1. Recommended Low Pressure Control Settings for Outdoor Air Cooled Condensing Units

R-22

R-404A/R-507

R-134a

*Minimum

Cut-In

Cut-Out

Cut-In

Cut-Out

Cut-In

Cut-Out

Temp. ˚F

PSI

PSI

PSI

PSI

PSI

PSI

50

70

20

90

35

45

15

40

55

20

70

35

35

10

30

40

20

55

35

25

10

10

30

10

45

25

13

0

0

15

0

25

7

8

0

-10

15

0

20

1

---

---

-20

10

0

12

1

---

---

-30

6

0

8

1"Hg.

---

---

* Minimum ambient or box temperature anticipated, Hi pressure control setting: R-22, 360 PSI; R-404A, R-507, 400 PSI; R-134a, 225 PSI.