Vent clearances and framing, A. pipe clearances to combustibles, B. wall penetration framing – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 38

Advertising
background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

38

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance

to vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

Figure 8.2 Wall Penetration

* Shows center of vent framing hole for top or rear venting. The center of the

hole is one 25.4 mm above the center of the horizontal vent pipe.

Figure 8.1 Horizontal Venting Clearances To Combustible

Materials

B. Wall Penetration Framing

Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must

frame a hole for the wall shield firestop(s). The wall shield

firestop maintains minimum clearances and prevents cold

air infiltration.
• The opening must be framed on all four sides using the

same size framing materials as those used in the wall

construction.

• DVP pipe - A wall shield firestop is required on one side

only on interior walls. If your local inspector requires a

wall shield firestop on both sides, then both wall shield

firestops must have a heat shield (refer to Section

16.B.) attached to them.

• SLP pipe - A wall shield firestop must be placed on each

side of an interior wall. A minimum 1-1/2 inch (38 mm)

overlap of attached heat shields must be maintained.

• See Section 10.H. for information for regarding the in-

stallation of a horizontal termination cap.

Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by noncom-

bustible materials such as concrete, a hole with diameter

one inch greater than the pipe is acceptable.
Whenever a non-combustible wall is penetrated, the wall

shield firestop is only required on one side and no heat

shield is necessary.

* When using SLP pipe, minimum clearances from the vent pipe to combustible

materials at inside wall firestops are:

Top: 2-1/2 in. (64 mm)

Bottom: 1/2 in. (13 mm)

Sides: 1 in. (25 mm)

(DVP-SLP Pipe Shown)

3 in. (76 mm)

top clearance *

1 in. (25 mm)

clearance

bottom & sides

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance *

1 in. (25 mm)

clearance

bottom & sides

Heat

Shield

Wall

Shield

Firestop

Heat

Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)

clearance around

vertical sections

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).

DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184

mm)

thick.

• If wall thickness is less than 4 in. (102 mm) the existing heat shields must be field

trimmed. If wall thickness is greater than 7-1/4 in. (184 mm) a DVP-HSM-B will be

required.

SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

194 mm thick).

• If wall thickness is less than 4-3/8 in. (111 mm) the existing heat shields must be

field trimmed. If wall thickness is greater than 7-5/8 in. (194 mm) a DVP-HSM-B will

be required.

A*

B*

C

D

350TRSI-AUF

350TRSILP-AUF

in.

39-3/4

22-3/8

38-3/4

21-3/8

mm

1010

568

984

541

C

D

A*

B*

10 in.

254 mm

10 in.

254 mm

10 in.

254 mm

12 in.

305 mm

Note: A 152 mm section of straight flue must

be attached to the fireplace before a 90° elbow.

Advertising
This manual is related to the following products: