Top vent - vertical termination no elbow, 3 ft. min. (914 mm) installing flue restrictor – Heat & Glo Fireplace 8000CF-OAK-IPI User Manual

Page 26

Advertising
background image

Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. R • 6/09

26

Top Vent - Vertical Termination

No Elbow

Figure 7.6

Note: If installing a vertical vent/termination off the top of the

appliance, the fl ue restrictor should be used.

V

1

V

1

= 50 ft. Max. (15.2 m)

V

1

= 3 ft. Min. (914 mm)

Installing Flue Restrictor

Figure 7.7

FLUE RESTRICTOR

Figure 7.8 fl ue restrictor

BREAK

HERE

1. Note location of fl ue restrictor (see Figure 7.7). Break

the fl ue restrictor into two pieces. Do this by bending the

part back and forth until it breaks (see Figure 7.8).

2. Match the amount of vertical in the system with the chart

to fi nd the appropriate position to set the fl ue restrictor

(see Figure 7.9).

1 2 3 4 5

SETTING

1 2 3 4 5

Figure 7.10

3. Center the fl ue restrictor on vent and secure in place

by using two self-tapping screws (see Figure 7.10).

Figure 7.9

- CHART -

Vertical

Top Vent

NG

Top Vent

LP

4’

1-1

No Restrictor

8’

2-2

1-2

15’

3-3

3-2

20’

3-4

3-3

25’

3-4

3-3

30’

4-4

3-4

35’

4-4

3-4

40’

5-4

4-4

45’

5-4

4-4

50’

5-4

4-4

Advertising
This manual is related to the following products: