background image

OM-950 Page 15

4-6. Weld Output Cables

For weld output cable replacements or extensions, contact your Factory

Authorized Service Agent.

NOTE

4-7. Electrical Service Guide

50/60 Hz

Single

Phase

Input Voltage

230

Input Amperes At Rated Output

47.5

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

50

Normal Operating

3

70

Min Input Conductor Size In AWG

4

12

Max Recommended Input Conductor Length In Feet (Meters)

87 (26)

Min Grounding Conductor Size In AWG

4

12

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.