W8635A EQUIPMENT INTERFACE MODULE

69-1339—2

2

Fig. 2. Mounting W8635A

Equipment Interface Module.

4.

Position the W8635A on the wall or on the cold air
return.

5.

Level the W8635A for appearance only; the device
functions properly even when not level.

6.

Use a pencil to mark the position of the mounting
holes on the wall or cold air return.

7.

Remove the W8635A from the wall or cold air
return and drill 3/16 in. holes in the wall (if drywall)
where marked. For firmer materials such as plaster
or wood, drill 7/32 in. holes.

8.

When mounting on the cold air return, drill a pilot
hole where marked.

9.

Gently tap the anchors (provided) into the holes
until flush with the wall.

10.

Reposition the W8635A over the holes.

11.

Loosely insert the screws into the holes and tighten
each screw.

WIRING

All wiring must comply with local electrical codes and
ordinances. See Fig. 4 through 6 wiring diagrams for
specific equipment applications. Refer to Table 2 for
terminal designations.

CAUTION

Voltage Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power before beginning installation.

1.

Loosen the terminal screws on the W8635A and
connect the system wires. See Fig. 3.

2.

Securely tighten each terminal screw.

Fig. 3. Wiring the W8635A terminals.

Table 2. Terminal Designations.

Fig. 4. 2H/2C single transformer.

Y2

W2

Y1

G

W1

C

R

RH

RC

1

2

3

MOUNTING
HOLES (2)

MOUNTING
SCREWS (2)

W8635

WALL

M16636

W8635A

Terminal

Designations

Function

1

To Communicating Thermostat
Terminal 1

2

To Communicating Thermostat
Terminal 2

3

To Communicating Thermostat
Terminal 3

R

24 Vac System Transformer

Rh

24 Vac Heating Transformer

Rc

24 Vac Cooling Transformer

C

24 Vac Transformer Common

G

Fan Relay

W1

Stage 1 Heat Relay

W2

Stage 2 Heat Relay

Y1

Stage 1 Cool Relay

Y2

Stage 2 Cool Relay

Green LED

Indicates Data Communication

FOR WRAPAROUND
CONNECTION—
STRIP 7/16 IN. (11 MM)

FOR STRAIGHT
CONNECTION—
STRIP 5/16 IN. (8 MM)

M16639

W8635

L1
(HOT)

L2

COOL 1
RELAY

HEAT 2
RELAY

FAN
RELAY

OT

OT

2

1

3

FACTORY INSTALLER JUMPERS.

M13429

C7089B
OUTDOOR
TEMPERATURE
SENSOR

1

T8635L

HEAT 1
RELAY

W8635A

C

R

RH
RC

1

2

3

Y2

W2

Y1

G

W1

COOL 2
RELAY

1

SYSTEM

TRANSFORMER