Compressors, Copeland compressors, Table 8. 3d/4d/6d solid state modules – Heatcraft Refrigeration Products H-IM-72A User Manual

Page 20: Table 9. typical voltage ranges, Table 10. unloader factors

Advertising
background image

20

Table 11. Oil Safety Switch

Pressure

Alarm

Copeland

MFGRS.

Model No. Diff. Psi (bar)

Circuit

Part No.

Cut-In

Cut-Out

Sentronic

7 – 9

12 - 14

Yes

085-0062-00

Penn

P45NCA-12

No

Ranco

P30-5826

Yes

Robertshaw

PD21-2502

9 (

±

2)

14

No

085-0088-00

Robertshaw

PD21-1006

Yes

Penn

P45NCB-3

Yes

085-0101-00

Robertshaw

LG21-2501

Yes

All controls are Manual Reset type with a 120 second nominal time delay at the rated voltage.

Compressors

The majority of the Heatcraft Parallel systems incorporate the
Copeland compressor. Other brand compressors are
available upon customer request. The compressors are solid
mounted to a base frame or mounted on the refrigerant
receiver. All reciprocating compressors incorporate oil floats.
Crankcase heaters will be installed and wired. Cylinder head
cooling fans will be installed on all low temperature

reciprocating systems or as directed by the specific
compressor manufacturer. A high pressure cutout and oil
failure control are installed and wired for each compressor.

Many compressors are available with unloading for capacity
control. The unloading of a compressor adds many capacity
steps to those normally available to an electronic controller.
Usually, the more steps available the better the load can be
matched.

Copeland Compressors

Table 8. 3D / 4D / 6D Solid State Modules

Control Voltage

Model

Copeland

Copeland

T.I.

Number

Kit

Number

Number

Number

115 - 230 Volts

3D-FSM

4D / 6D

998-0524-00

071-0524-00

31AA-1600E

Table 9. Typical Voltage Ranges

Voltage

60 Hertz Rating

50 Hertz Rating

Code

Rating

Min.

Max.

Rating

Min.

Max.

B

230-1

207

253

-

-

-

C

208/230-3

187

253

200/220-3

180

240

D

460-3

414

506

380/420-3

342

462

E

575-3

518

633

500-3

450

550

K

208/230/460-3

187

506

200/380/400-3

180

440

M

-

-

-

380/420-3

342

462

N

230/460-3

207

506

200/400-3

180

440

U

200-3

180

220

-

-

-

Refer to voltage rating of specific models.

Table 10. Unloader Factors

Model

Factors

3D

See Copeland Application Bulletin Number AE 21-1278
Moduload - Capacity Control for 3D Compressors

Full Load

One Bank

Two Bank

Unloading

Unloading

Performance

HT

MT

LT

HT

MT

LT

HT

MT

LT

CAPACITY

1.00

1.00

1.00

.50

.50

.50

-

-

-

4D

POWER

1.01

1.03

1.02

.56

.56

.56

-

-

-

AMPS

1.01

1.03

1.02

.60

.60

.74

-

-

-

CAPACITY

1.00

1.00

1.00

.70

.70

.70

.36

.36

.36

6D

POWER

1.01

1.03

1.02

.70

.71

.72

.40

.42

.43

AMPS

1.03

1.04

1.02

.75

.77

.84

.55

.60

.72

Multiply compressor rating data by above factors when used with blocked suction unloading.
Refer to Copeland AE 17-1287 for Demand Cooling Restrictions on unloading.

Advertising