Table 17. Henry Relief Valve Capacity Ratings

Pounds of Air per Minute for all Refrigerants Except Ammonia R717

TYPE

CATALOG SIZE CONNECTION STANDARD PRESSURE SETTINGS PSIG

NUMBER

INLET

OUTLET

350

400

425

450

ANGLE

526E

3/8 M.P.T.

3/8 FLARE

10.2

11.6

12.3

13.0

527E

1/2 M.P.T.

5/8 FLARE

28.5

32.4

34.4

36.3

5231

3/8 M.P.T.

3/8 FLARE

11.2

12.7

13.5

14.3

5231-A

3/8 M.P.T.

1/2 FLARE

18.6

21.1

22.4

23.7

STRAIGHT

5231

1/2 M.P.T.

5/8 FLARE

18.6

21.1

22.4

23.7

THROUGH

5232

1/2 M.P.T.

5/8 FLARE

28.1

32.0

33.9

35.8

5240-1/2

1/2 M.P.T.

3/4 F.P.T.

41.2

46.8

49.1

52.5

5242-3/4

3/4 M.P.T.

3/4 F.P.T.

41.2

46.8

49.1

52.5

5244-1

1 M.P.T.

1 F.P.T.

74.0

84.2

89.3

94.4

5246-1-1/4

1-1/4 M.P.T.

1-1/4 F.P.T.

129.7

147.5

156.4

165.4

Table 18. Discharge Piping Table

MAXIMUM LENGTH OF DISCHARGE PIPE IN FEET

* FOR 400 PSIG PRESSURE SETTING

RELIEF DEVICE

CAPACITY

SOFT COPPER TUBE O.D.

SCHEDULE 40 PIPE

LBS. AIR/MIN.

3/8”

1/2”

5/8”

1/2”

3/4”

1”

1

1

/

4

1

1

/

2

2”

10

3

1

/

2

19

1

/

4

61

108

445

12

2

1

/

2

12

1

/

4

44

75

308

14

2

9

1

/

2

32

56

228

18

5

1

/

4

19

1

/

4

33

137

20

4

1

/

4

16

28

110

371

25

2

1

/

2

9

1

/

2

18

72

238

30

2

7

12

49

165

35

2

5

1

/

4

9

37

121

40

3

1

/

2

7

28

93

366

50

2

1

/

2

4

18

60

233

70

3

9

30

119

257

80

2

7

23

91

198

90

2

5

18

72

156

125

3

10

37

81

282

150

2

7

26

56

196

For Relief Devices set at 400 psig
• Obtain the capacity at 400 psig setting.
• Locate this capacity or the nearest larger capacity in the left-hand column of the discharge piping table above and read across to obtain the
maximum lengths for each tube and pipe size.
For relief devices set at 350 psig, use the above table and multiply by .75 to determine maximum lengths.
For relief devices set at 425 psig, use the above table and multiply by 1.15 to determine maximum lengths.
For relief devices set at 450 psig, use the above table and multiply by 1.25 to determine maximum lengths.