Central Station Communications

182

MS-9200UDLS PN 52750:E1 01/27/09

5.1 Transmittal Priorities

The integral communicator transmits highest priority events first. Events, in terms of priority, are
listed below in descending order:

1. Alarms (highest priority level)

 Pull stations
 Waterflow
 Smoke detector
 Other alarm types

2. Supervisory Zone

3. System Troubles

 Zone disabled
 Fire drill
 AC fail (after delay)
 Zonal faults
 Earth fault
 Low battery
 Telephone line fault
 Notification Appliance Circuits fault
 Communication trouble
 Annunciator trouble
 System off normal

4. Restoral Reports

 Zone alarm
 Supervisory
 Zone(s) enabled
 Fire drill
 AC
 Zone fault
 Earth
 Battery
 Telephone line
 Notification Appliance Circuits
 Communication
 Annunciator trouble
 System off normal

5. 24 Hour Test (lowest priority)

Red LEDs are provided on the circuit board to identify which telephone line is activated. Also, a
green LED labeled Kissoff will turn on whenever the control panel has successfully transmitted
reports to the Central Station. The Kissoff LED may turn on several times during communications
with a Central Station.