ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS

3

63-2540—9

Timing (At Rated Torque and Voltage):

Drive Open:

ML4105, ML8105: 15 sec maximum, 14 sec typical.

ML4115: 25 sec maximum, 18 sec typical.

ML8115: 25 sec maximum, 22 sec typical.

Spring Close: 15 seconds.

Cycling Requirements:

Prolonged holding-period (1 year) testing of these actuators

has been performed with no spring return failures. The

actuator and the internal spring are designed to require no

special cycling during long-term holding.

Honeywell recommends following all local, state and national

codes for periodic testing of the entire smoke control

system. Refer to National Fire Protection Association (NFPA)

National Fire Codes®: NFPA90A, NFPA92A and NFPA92B

for your application.

NFPA recommends periodic examination of each fire/smoke

damper (semi-annually or annually) to ensure proper

performance.

Design Life (at Rated Voltage): 60,000 full stroke cycles.

Approvals: See Table 2.

Environmental Protection Ratings: See Table 3.

Accessories:

201391 Shaft Adapter for 3/8 in. shafts (not supplied with

actuator).

205649 Mounting Bracket (not supplied with actuator).

Table 2. Approvals.

Table 3. Environmental Ratings.

Fig. 1. ML4105/ML4115/ML8105/ML8115

dimensional drawing in in. (mm).

ML4105

ML4115A,B

ML4115C,D

ML8105,

ML8115

A,B

C1008,

D1007

C1016,

D1015

UL/cUL

X

X

X

X

UL873 Plenum

Rating, File No.

E4436; Guide

No. XAPX.

X

X

X

X

X

CE

X

X

X

C-TICK

X

X

X

All Devices

ML4105C1008

ML4105D1007

ML4105C1016

ML4105D1015

ML4115C,D

NEMA1

IP40

IP54

2 (51)

1 (25)

5/8

(17)

6 3/8

(161)

7 1/2

(192)

4 (102)

7/8 (22)

5 1/8 (129)

2 (51)

3 5/16 (84)

1/16 (2)

M13053A

ML4115/ML8115 HAVE SMALLER

HUB WITH TWO SET SCREWS.

ML4105/ML8105 HAVE LONGER

HUB WITH FOUR SET SCREWS.

1