Installation, Wiring, Caution – Honeywell ML4105 User Manual

Page 5: Warning

Advertising
background image

ML4105, ML4115, ML8105, ML8115 FAST-ACTING, TWO-POSITION ACTUATORS

5

63-2540—9

Installation

CAUTION

Device Malfunction Hazard.

Improper set screw tightening causes device

malfunction.

Tighten set screws with proper torque to prevent

damper shaft slippage.

CAUTION

Actuator Damage Hazard.

Using actuator as shaft bearing causes device

damage.

Use actuator only to supply rotational torque. Avoid

any side loads to actuator output coupling bearings.

To install actuator, proceed as follows:

1. Place actuator over damper shaft; and hold mounting

bracket in place. See Fig. 2.

2. Mark screw holes on damper housing.

3. Remove actuator and mounting bracket.

4. Drill or center-punch holes for mounting screws (or use

no.10 self-tapping sheet metal screws).

5. Turn damper blades to desired normal (closed) position.

6. Place actuator and mounting bracket back into position

and secure bracket to damper box with sheet metal

screws.

7. Tighten set screws securely into damper shaft using

minimum 30 lb-in., maximum 60 lb-in. torque. Use

1/8 in. or 3 mm Allen wrench (see Specifications for

details) to tighten set screws.

Wiring

See Fig. 4 through 8 for typical wiring diagrams.

WARNING

Electrical Power Hazard.

Line voltage can cause death or serious injury and

short equipment circuitry.

Disconnect power supply before installation.

CAUTION

Electrical Shock or Equipment Damage Hazard.

Low voltage can shock individuals or short

equipment circuitry.

Disconnect power supply before installation.

IMPORTANT

1. All wiring must comply with local electrical codes,

ordinances and regulations.

2. Voltage and frequency of transformer used with

ML8105 and ML8115 must correspond with the

characteristics of power supply and actuator.

3. Use wires rated for at least 75°C (167°F).

Fig. 4. Typical 24 Vac wiring.

Fig. 5. Typical 120 Vac wiring.

Fig. 6. Typical 230 Vac wiring.

Fig. 7. 230 Vac terminal-strip wiring.

Fig. 8. 230 Vac terminal-strip wiring with a thermal fuse.

NOTE: Terminal strip included with ML4105C1008 and

ML4105D1007.

L1

24 VAC

L2

RED
BLACK

M17585A

( )

( )

L1

120 VAC

L2

WHITE

BLACK

M17589A

( )

( )

L1

230 VAC

L2

BLUE

BROWN

M17588A

( )

( )

L1

1

2

3

L1

L2

M17586A

( )

( )

230 VAC

L1

1

2

200 F

93 C

3

L1

L2

M17587A

( )

( )

230 VAC