5-5

5.2

Wiring of Control Circuit Terminals

FM CM1 PLC P24 FW

8

7

6

5

4

3

2

1

H

O

OI

L

CM2 12

11

AL2 AL1 AL0

Frequency meter

Input intelligent terminal

Frequency setting

(500

to 2 k

)

Fault alarm

For output
Intelligent terminal
27 VDC 50 mA
50 mA max

Current input

DC 4 to 20 mA

RY

RY

SINK TYPE wiring

(Factory settings)

FM CM1 PLC P24 FW

8

7

6

5

4

3

2

1

H

O

OI

L CM2 12

11

AL2 AL1 AL0

Frequency meter

Input intelligent terminal

Frequency setting

(500

to 2 k

)

Fault alarm

For output
Intelligent terminal
27 VDC 50 mA
50 mA max

Current input

DC 4 to 20 mA

RY

RY

SOURCE TYPE wiring

NOTE 1: When an output intelligent terminal is used, be sure to install a surge absorbing

diode in parallel with the relay (RY). Otherwise, the surge voltage created when
the relay (RY) goes ON or OFF may damage the output intelligent terminal cir-
cuit.

NOTE 2: Use a twisted and shielded wire for the signal line, and cut the shielded covering

as shown in the diagram below. Make sure that the length of the signal line is 20
meters or less.