Section 3

WattMaster WHP

3-28

Programming

Setpoint Screen #3

Setpoint Screen #4

Setpoint Screen #5

If the controlling water temperature drops below this Setpoint,
the Heat Addition or Boilers begin to stage on. As the
temperature continues to drop below the Setpoint by the
Deadband amount, an additional stage is added. Each
additional stage can only activate if the temperature drops
below the Setpoint by the number of active stages times the
deadband value.

Example: There are 2 stages on, a 3

°

deadband and the setpoint

is 79

°

79

°

- 2 x 3

°

= 73

°

before stage 3 can activate

WHP Loop Setpoints

HEATING ADDITION

Setpoint......: xx

°

F

Stage Deadband: xx

°

F

Minimum

Default

Maximum

Setpoint

50

°

F

76

°

F

99

°

F

Stage Deadband

1

°

F

3

°

F

10

°

F

The Staging Delay period must also be satisfied before an
additional boiler or heat addition stage can be activated.
The maximum number of heat addition stages are programmed
on this screen also.

WHP Loop Setpoints

HEATING ADDITION

Stage Delay...: x M

Minimum

Default

Maximum

Stage Delay

1 Minute

1 Minute

60 Minutes

If the outdoor air temperature drops below this setpoint, the
pump will be energized to prevent the water lines from
freezing.

WHP Loop Setpoints

OA FREEZE PROTECTION

Setpoint.....: xx

°

F

Minimum

Default

Maximum

Setpoint

-50

°

F

40

°

F

50

°

F