EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER

3

95-7520—02

Fig. 3. W7753A DIN rail mounting.

Wiring

All wiring must comply with applicable electrical codes and

ordinances or as specified on installation wiring diagrams.

Controller wiring on the W7753A is terminated to the screw

terminal blocks located on the top and the bottom of the

controller.

NOTES:

For multiple controllers operating from a single

transformer, the same side of the transformer

secondary must be connected to the same power

input terminal in each controller. The ground

terminal (1 on the W7753A) must be connected to

a verified earth ground for each controller in the

group (see Fig. 5). (Controller configurations are

not necessarily limited to three controllers, but the

total power draw including accessories cannot

exceed 100 VA when powered by the same

transformer (U.S. only). See System Engineering

form 74-2964 for power wiring recommendations.)

All loads on an Excel 10 W7753A Controller must

be powered by the same transformer that powers

the Excel 10 W7753A Controller. A W7753A

Controller can use separate transformers for

controller power and load power.

Keep the earth ground connection (terminal 1)

wire run as short as possible. Refer to Fig. 9

through 14.

Do not connect the analog or digital ground

terminals (5, 8, 11, 27 and 30) to earth ground.

Refer to Fig. 9 through 14.

Power

The 24 Vac power from an energy-limited Class II Power

Source must be provided to each W7753A Controller. To

conform to Class II restrictions (U.S. only), transformers must

not be larger than 100 VA.

A transformer that meets CE mark requirements and that

meets the Low Voltage Directive (LVD) requirements must be

used in Europe for all installations of this product. More than

one W7753A Controller can be powered by a single

transformer. Fig. 4 shows power wiring details for a single

controller and Fig. 5 depicts multiple controllers using one

transformer.

IMPORTANT

Use the heaviest gauge wire available, up to 14

AWG (2.0 mm

2

) with a minimum of 18 AWG

(1.0 mm

2

), for all power and earth ground wiring.

Screw type terminal blocks are designed to accept

up to two 14 AWG (2.0 mm

2

) conductors, one on

each side of the terminal screw. More than two wires

that are 14 AWG (2.0 mm

2

) can be connected with a

wire nut. Include a pigtail with this wire group and

attach the pigtail to one side of the terminal block.

Fig. 4. Power wiring details; one Excel 10 per transformer.

NOTES:

Unswitched 24 Vac power wiring can be run in the

same conduit as the E-Bus cable.

Maintain at least three-inch (76 mm) separation

between Triac outputs and E-Bus wiring

throughout the installation.

See the following IMPORTANT on Heating and Cooling

Equipment (UL 1995, U.S. only).

IMPORTANT

If the W7753A Controller is used on Heating and

Cooling Equipment (UL 1995, U.S. only) and the

transformer primary power is more than 150 volts,

connect the transformer secondary to earth ground

(see Fig. 6). For these applications, only one

W7753A Excel 10 controller can be powered by each

transformer.

M6857

1

2

3

M12681

CONNECT POWER TO

TERMINALS 24 AND 25

TRIAC LINES

TO ACTUATORS

AND

CONTACTORS

TRANSFORMER

W7753A

EARTH

GROUND

20

22

24

25

1

OUTPUT

DEVICE

POWER