Location of your laundry center, Gas supply requirements – FRIGIDAIRE 134897500B User Manual

Page 5

Advertising
background image

5

60 SQ. IN.

(387.1 SQ. C M)

60 SQ. IN.

(387.1 SQ. C M)

Closet Door

0 IN.

(0 CM)

DRYER

WASHER

0 IN.

(0 CM)

1 IN.

(2.54 CM)

0 IN.

(0 CM)

60 SQ. IN.

(387.1 SQ. C M)

60 SQ. IN.

(387.1 SQ. C M)

LOCATION OF YOUR LAUNDRY CENTER

DO NOT INSTALL YOUR LAUNDRY CENTER:
1.In an area exposed to dripping water or outside weather conditions.
2.In an area where it will come in contact with curtains or drapes.
3.On carpet. Floor MUST be solid with a maximum slope of 1 inch (2.54 cm).

INSTALLATION IN RECESS OR CLOSET
1.A laundry center installed in a bedroom, bathroom, recess or closet, MUST be exhausted outdoors.
2.No other fuel burning appliance shall be installed in the same closet as the Gas laundry center.
3.Your laundry center needs the spacearound it for proper ventilation.

DO NOT INSTALL YOUR LAUNDRY CENTER IN A CLOSET WITH A SOLID DOOR.

4.A minimum of 120 square inches (774.2 square cm) of opening, equally divided at the top and bottom of the door, is required.

Air openings are required to be unobstructed when a door is installed. A louvered door with equivalent air openings for the full
length of the door is acceptable.

5.The following illustrations show minimum clearance dimensions and air openings for proper operation in a recess or closet

installation.

The laundry center may be exhausted four (4) ways with rear
flush installation:
1. Straight back
2. Down (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid

duct and 1 elbow down)

3. Left (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid

duct, 1 elbow down and 1 elbow left)

4. Right (8 inch [20.32 cm] length of 4 inch [10.16 cm] rigid

duct, 1 elbow down and 1 elbow right)

To exhaust up, add an 11 inch (27.94 cm) length of standard 4
inch (10.16 cm) diameter duct and a 90° elbow. The unit will
be positioned about 4½ inches (11.43 cm) away from the wall
(flush to wall exhausting may be done by going below the dryer
then sideways).

An exhaust hood positioned
to line up with the dryer
exhaust can be installed
directly through the outside
wall. To exhaust to the side
or down, add an 8 inch
(20.32 cm) length of standard
4 inch (10.16 cm) diameter
duct and a 90° elbow.

GAS SUPPLY REQUIREMENTS

1.Installation MUST conform with local codes, or in the absence

of local codes, with the National Fuel Gas Code, ANSI Z223.1
(latest edition) or in Canada, the current AN/CGA B149.

2.The gas supply line should be of 1/2 inch (1.27 cm) pipe.

3.If codes allow, flexible metal tubing may be used to connect

your dryer to the gas supply line. The tubing MUST be
constructed of stainless steel or plastic-coated brass.

4.The gas supply line MUST have an individual shutoff valve.

5.A 1/8 inch (0.32 cm) N. P. T. plugged tapping, accessible for

test gage connection, MUST be installed immediately
upstream of the gas supply connection to the dryer.

6.The dryer and its individual shutoff valve MUST be

disconnected from the gas supply piping system during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.45 kPa).

7.The dryer MUST be isolated from the gas supply piping system

by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures
equal to or less than 1/2 psig (3.45 kPa).