BUILD AND INSTALL THE
ZONELINE BASE PLATFORM

1. Construct a 23

1

4

″ min. x 23

1

4

″ min. square platform.

NOTE:

The platform must have a load-bearing

capacity of 175 lbs. minimum.

1

Installation Instructions

18

WALL PLENUM AND ARCHITECTURAL LOUVER INSTALLATION

• Install the appropriate wall plenum through the exterior wall in accordance with the Installation Instructions

provided with the plenum.

IMPORTANT:

The wall plenum is not designed to carry structural loads.

Proper wall header construction is required. The plenum requires proper
flashing, shim and caulk for a weather resistant installation.

Properly square and
level plenum.

Proper header for
structural support.
Apply proper caulking
and flashing.

Architectural

Louver—RAVAL1

Exterior/Outside Wall

Case

Wall Plenum

RAVWP6 – 6

″D x 19

3

4

″W x 32″H

RAVWP8 – 8

″D x 19

3

4

″W x 32″H

RAVWP12 – 12

″D x 19

3

4

″W x 32″H

RAVWP15 – 15

″D x 19

3

4

″W x 32″H

2. Place the platform in the utility closet with the

following clearance between it and the interior
surface of the walls/door/panel:
4

min. from front of the case – Unit to be

installed through FRONT of case

5

min. from front of the case – Unit to be

installed through SIDE of case

3

min. from two sides of the case

3. Align the platform with the opening of

the wall plenum and secure to the floor
using appropriate brackets and bolts.

23

1

4

″ min.

23

1

4

″ min.

8

″ min.

for drain
access

Cutout for drain
connection