Installation instructions, Install the drain, Ductwork – GE 49-7419-2 User Manual

Page 19: Cfm recommendations, Side view

Advertising
background image

INSTALL THE DRAIN

An external or an internal drain must be attached to
the drain connector.

External Drain

Attach a 90° PVC elbow to the unit’s female 3/4

″ NPT

drain connector. Use the other end of the elbow to
run a 3/4

″ Sch.40 PVC pipe through the knockout

holes of both the wall plenum and the architectural
louver to the outside. Seal the gap between the
plenum hole and PVC tube. See the Installation
Instructions in the RAVAL1.

Internal Drain

Attach PVC to the unit’s female 3/4

″ NPT drain

connector. See the Installation Instructions in the
RAVAL1. Local codes may apply.

2

DUCTWORK

Prepare the closet ductwork for later connection to
the case.
The total flow rate (CFM) and external static pressure
(ESP) available can be estimated from the chart below.
Use these charts to select your fan speed setting. The
collar on top of the case accepts standard 10

″ duct.

Pull all duct tight. Extra duct slack can greatly increase
static pressure.
CAUTION: Flex duct can collapse and cause airflow
restrictions. Do not use flex duct for 90° bends or
unsupported runs of 5 ft. or more.

3

Installation Instructions

19

Your airflow should be balanced based on many
factors, such as available ESP, room CFM, and
ductwork. Consult an HVAC engineer for proper
applications. External static pressure (ESP) can be
measured with a manometer or pitot tube. Once this
ESP is established, you can calculate the CFM using
the above chart.

CFM Recommendations

9,000 BTU

12,000 BTU

18,000 BTU

275

300

325

350

375

400

450

500

550

• = Recommended Mid Range

Higher CFMs tend to increase Sensible capacity,
enhance room circulation and increase duct noise,
while lower CFMs tend to increase Latent capacity
and reduce noise.

Side View

Inside wall

Female drain
fitting

3

4

PVC

90° Elbow

PVC
(External drain)

PVC
(Internal drain)

Side View

Inside wall

Female drain
fitting

3

4

Airflow – CFM@230 Volts and @ 265 Volts

Indoor Fan CFM

DUCT SELECT SWITCH

UP

DOWN

ESP

(in. water)

High
CFM

Medium

CFM

Medium

CFM

Low

CFM

0.0
0.1
0.2
0.3
0.4

390
370
350
330
310

340
320
300
280
260

340
320
300
280
260

305
290
270
250
230

0.0
0.1
0.2
0.3
0.4

475
450
425
400
375

390
370
350
330
315

390
370
350
330
315

350
325
300
275
250

0.0
0.1
0.2
0.3
0.4

630
610
590
570
550

545
530
515
495
475

545
530
515
495
475

490
480
470
455
440

AZ75(H/E)09

AZ75(H/E)12

AZ75(H/E)18

To correct for 208 volts: 0.91