GE Zenith Controls

15

ZTX Operation and Maintenance Manual (72R-1000)

Troubleshooting

Symptom

Possible Cause

Corrective Action

S1 or S2 Available LED not lit

Sources either fully or partially unacceptable

Check for under voltage

S1 or S2 breakers open

Check for missing phase (s)
Check for under frequency

ATS will not retransfer Load

T - Timer has not expired

back to Utility

Automatic Exerciser is in process
S1 Utility fully or partially unacceptable

ATS does not transfer Load to S2

S2 Generator fully or partially unacceptable

Set motor-saver to dropout below

(generator)

Motor loads on system creating enough back-

ATS Fail setpoint

EMF to keep missing phase from falling below
Fail setpoint.

S2 Generator will not start

X1 or X2 not connected

Check Generator Start wiring

S2 Generator will not shut down

U - Timer not expired

Wait for U timer to expire

Automatic Exerciser in process

All LEDs off

Keypad connector unplugged at Controller
Both source breakers open

ATS will not transfer in-phase

In-Phase monitor not on

Turn on In-Phase monitor

Frequency difference between S1 and

Adjust Generator governor to hold

S2 greater than 2Hz.

freqency closer to Utility

ATS will not retain a

Battery dead or missing

Replace battery with a fresh industrial

Set Automatic Exerciser

grade Alkaline battery

Timer/In-Phase LED constantly on

Both sources locked in frequency or one

Turn In-Phase monitor off

source greater than 20° out of phase

S1 and S2 LEDs Blinking

Phase Rotation Mis-match between sources

Rewire sources to be same rotation

S1 Position LED Blinking

SN limit switch bad or intermittent

Check connection or SN limit switch

S2 Position LED Blinking

SE Limit switch bad or intermittent

Check connection or SE limit switch

Both S1 and S2 Positioin

Solenoid bad or disconnected

Requires CANCEL key to clear -

LEDs Blinking

ATS contactor in mid-position

check Solenoid
Requires CANCEL key to clear -
Check both limit switches

Service must be performed by qualified personnel.

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Table 9