Installation

(cont’d)

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

System Voltage Settings

ZTX controller boards are preconfigured to the system
voltages specified at the time of order. Exact system volt-
ages are normally set at the factory, however, depend-
ing on the actual application and system nominal volt-
age, ZTX control boards are capable of being adjusted
slightly, to meet different source characteristics for
voltage as well as frequency. (See Table 5)

Figure 6 (on right) shows the variations each of the 3
basic types of controllers can be adjusted to within its
nominal voltage range. Position Jumpers JP1 and JP2,
as needed for voltage. Position JP3 for frequency.
As with any other Jumper setting, always remove power
completely from the controller before making changes.

Note: Do not change voltage Jumper positions
without consulting service or technical support.
Arbitrarily changing voltage jumpers can adversely
affect ATS operation.

Type 1

Type 2

Type 3

Type 4

Frequency

120V

208 - 240VAC

380 - 416VAC

440 - 480VAC

JP1

JP2

JP1 JP2

JP1 JP2

JP1 JP2

JP3

B

B

208

A

B

380 B

B

440

B

A

50 Hz

A

-

-

220

B

A

416 A

B

480

A

A

60 Hz

B

-

-

240

A

A

-

-

-

-

-

-

-

-

Table 5

Figure 6

240/480

B

A

JP1

JP2

208/416

B

A

JP1

JP2

120/380

B

A

JP1

JP2

220/440

B

A

JP1

JP2

Voltage / Frequency Selection Jumper Settings

50Hz

B

A

JP3

60Hz

B

A

JP3