Installation, Power connections, Danger – GE Industrial Solutions ZTX Series User Manual

Page 4

Advertising
background image

2

GE Zenith Controls

ZTX Operation and Maintenance Manual (72R-1000)

GENERATOR

TERMINALS

N

BR

UTILITY

TERMINALS

LOAD

TERMINALS

T1

T2

T3

N1

N3

E1

E3

E2

N2

T = Load N = Utility E = Generator

OPTIONAL A4 CONTACT

TION

OPERATES WHEN IN

ERAT

UTILITY POSITION

ILITY

OPTIONAL A3 CONTACT

TION

OPERATES WHEN IN

ERAT

GENERATOR POSITION

NERA

SWITCH
POSITION
INDICATOR

JP

Install

load

cables

first.

Tip!

Table 1

Screw Type Terminals for External Power Connections

Switch Size

(Amps)

40
80

100
150

Utility, Generator and Load Terminals

1

#8 to 3/0 AWG

Cable Per Pole

Range of Wire Sizes

1

#8 to 3/0 AWG

1

#8 to 3/0 AWG

1

#8 to 3/0 AWG

Fully Rated Neutral Bar (When Required)

3

#8 to 1/0 AWG

No. of Cables

Range of Wire Sizes

3

#8 to 1/0 AWG

3

#8 to 1/0 AWG

3

#8 AWG to 300 MCM

200, 225, 250*

300, 400

1

#6 AWG to 250 MCM

1

#4 AWG to 600 MCM

3

#6 AWG to 300 MCM

3

#4 AWG to 300 MCM

* IEC Rating Only

Installation

(cont’d)

Figure 1 - Power Panel

Power Connections

GE Zenith transfer switches are supplied with UL listed

solderless screw type terminals as standard for the

Normal, Emergency and Load power connections.

Table 1 lists the number and sizes of cable lugs supplied

as standard for each switch amp rating.

DANGER

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Connect the Normal, Emergency, and Load conductors

to the clearly marked terminals on the transfer switch.

Remove surface oxides from cables by cleaning with a

wire brush. Verify that all connections are correct before

tightening the lugs. All cable lug connections must be

tightened to the proper torque values as shown in Table 2.

NOTE

:

Do not run cables or wiring behind
front-connected transfer switches.