Installation instructions, Warning, Caution – GE GEH50DXSRGA User Manual

Page 16: Condensation drain tubes, Relief valve, Water supply connections, Typical installation

Advertising
background image

CONDENSATION DRAIN TUbES

This unit has a condensation tray. The water collected in the

tray drains out of the tube coming off the back of the unit.

Two flexible hoses are included with this unit. It is important

that both of these hoses are attached to the two drain ports

coming off the back of the unit. Attach one end of the longer

6’ (1.8 m) hose to the lower drain port on the back of the unit,

underneath the rear cover. direct

the other end to a drain in the floor

or no higher than 3’ (0.9 m) above

the floor. If such drain is unavailable,

a condensate drain pump (not

provided) must be purchased and

installed. Attach the shorter 3”

(7.6 cm)hose to the top drain port.

Installation Instructions

RELIEf VALVE

WARNING:

The pressure rating of the relief

valve must not exceed 150 PSI (1.03 kPa), the maximum

working pressure of the water heater as marked on the

rating plate.
The BTuH rating of the relief valve must not be less than the

input rating of the water heater as indicated on the rating

label located on the front of the heater (1 watt=3.412 BTuH).
Connect the outlet of the relief valve to a suitable open drain

so that the discharge water cannot contact live electrical

parts or persons and to eliminate potential water damage.
Piping used should be of a type approved for hot water

distribution. The discharge line must be no smaller than the

outlet of the valve and must pitch downward from the valve

to allow complete drainage (by gravity) of the relief valve

and discharge line. The end of the discharge line should

not be threaded or concealed and should be protected

from freezing. no valve of any type, restriction or reducer

coupling should be installed in the discharge line.

A new combination temperature and pressure-relief

valve, complying with the Standard for Relief Valves and

Automatic Gas Shut-Off devices for Hot Water Supply

Systems, AnSI Z21.22, is supplied and must remain installed

in the opening provided and marked for the purpose on

the water heater. no valve of any type should be installed

between the relief valve and the tank. Local codes shall

govern the installation of relief valves.

CAUTION:

To reduce the risk of excessive pressures and

temperatures in this water heater, install temperature

and pressure protective equipment required by local

codes and no less than a combination temperature and

pressure relief valve certified by a nationally recognized

testing laboratory that maintains periodic inspection of

production of listed equipment or materials, as meeting

the requirements for Relief Valves and Automatic Gas

Shutoff devices for Hot Water Supply Systems, AnSI

Z21.22. This valve must be marked with a maximum set

pressure not to exceed the marked maximum working

pressure of the water heater. Install the valve into an

opening provided and marked for this purpose in the

water heater, and orient it or provide tubing so that

any discharge from the valve exits only within 6 inches

above, or at any distance below, the structural floor, and

does not contact any live electrical part. The discharge

opening must not be blocked or reduced in size under

any circumstances.

WATER SUPPLy CONNECTIONS

Refer to the illustration below for suggested typical installation.

The installation of unions or flexible copper connectors is

recommended on the hot and cold water connections so that

the water heater may be easily disconnected for servicing if

necessary. The HOT and COLd water connections are clearly

marked and are 3/4” nPT on all models.
NOTE: Install a shut-off valve in the cold water line near the

water heater. This will enable easier service or maintenance

of the unit later.
IMPORTANT:Do not apply heat to the HOT or COLD water

connections. If sweat connections are used, sweat tubing

to adapter before fitting the adapter to the cold water

connections on heater. Any heat applied to the hot or cold

water connection will permanently damage the internal

plastic lining in these ports.

TyPICAL INSTALLATION

3” (7.6 cm)

hose

6’ (1.8 m)

hose

To cold

water

supply

Jacket access panel

Relief valve

discharge line to

suitable open drain

Jacket access panel

Auxiliary catch

pan 2” (5.1 cm)

maximum

Drain valve

Electrical junction

box (use only

copper conductors)

Hot water

outlet to fixtures

6” ( 15.2 cm)

air gap

Shut-off valve

Union

Temperature and

pressure-relief valve

(shown in different

location for clarity)

Union

Thermal expansion

tank (if required)

To electrical

distribution panel

16

Advertising