Installation instructions, Warning, Notice – GE GEH50DXSRGA User Manual

Page 17: Electrical connections

Advertising
background image

Installation Instructions

17

TO fILL THE WATER HEATER

WARNING:

The tank must be full of water

before heater is turned on. The water heater warranty

does not cover damage or failure resulting from

operation with an empty or partially empty tank.
Make certain the drain valve is completely closed.
Open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to allow the air to

vent from the water heater and piping.
A steady flow of water from the hot water faucet(s)

indicates a full water heater.

ELECTRICAL CONNECTIONS

A separate branch circuit with copper conductors, overcurrent

protective device and suitable disconnecting means must be

provided by a qualified electrician.
All wiring must conform to local codes or latest edition of

national Electrical Code AnSI/nFPA 70.
The water heater is completely wired to the junction box at the

top of the water heater. An opening for 1/2” or 3/4” electrical

fitting is provided for field wiring connections.
The voltage requirements and wattage load for the water

heater are specified on the rating label on the front of the

water heater.

The branch circuit wiring should include either:

1. Metallic conduit or metallic sheathed cable approved

for use as a grounding conductor and installed with

fittings approved for the purpose.

2. nonmetallic sheathed cable, metallic conduit or

metallic sheathed cable not approved for use as a

ground conductor shall include a separate conductor

for grounding. It should be attached to the ground

terminals of the water heater and the electrical

distribution box.

WARNING:

Proper ground connection is

essential. The presence of water in the piping and water

heater does not provide sufficient conduction for a

ground. Nonmetallic piping, dielectric unions, flexible

connectors, etc., can cause the water heater to be

electrically isolated.

Water heater junction box

Ground screw

Junction box cover

240V

L2

L1

NOTICE:

do not mis-wire electrical connections. 240V AC must be

applied across L1 and L2 wires as shown in ‘Water heater

junction box’ illustration. Failure to do so will VOId the

warranty, and can result in 120V applied to water heater,

which may damage the compressor or other electrical

components.
If 4-conductor wire is supplied to the water heater, cap the

neutral, and connect the remaining wires as illustrated.
nOTE REGARdInG uTILITY POWER-MAnAGEMEnT dEVICES

(Sometimes called Peak Load Reduction Switches):
Some power-management switching devices or even some

basic timer switches exist that REduCE voltage from 240V

to 120V during high-electricity-demand periods. These

devices must be removed from the circuit providing power

to the water heater because of the potential unit damage

noted above.
However, switching devices which cut power from 240V to

0V on a periodic basis are acceptable.

Advertising