Section 6 — Scheduled Maintenance

Guardian Liquid-cooled 10 kW, 15 kW, 20 kW and 25 kW Generators

Maintenance

Level 1

Level 2

Level 3

Level 4

Tasks

Recom-

Task

Required

Task

Required

Task

Task

mended

Comp.

to be done

Comp.

to be done Comp.

Required

Comp.

to be done

(Date-

3 months/

(Date-

Semi-

(Date-

to be done

(Date-

monthly/

Initials)

Break-in

Initials)

annually/

Initials)

Annually/

Initials)

10 hrs.

30 hrs.

50 hrs.

100 hrs.

1. Disable the unit from

operating per the first page
warning.

2. Check the engine oil level.

Adjust as necessary.

3. Check the engine coolant

level. Adjust as necessary.

4. Check the engine coolant

thermal protection level.
Correct as necessary.

5. Check the natural gas

delivery system on gas
engine driven units.
Tighten connections as
necessary.

6. Check the diesel fuel

supply level for diesel
engine driven units. Fill
as necessary.

7. Drain water and sediment

from the diesel fuel tank on
diesel engine driven units.

8. Drain water from the fuel

line water separator on
diesel engine driven units
if the unit is equipped with
one.

9. Check the air inlets and

outlets for debris. Clean as
necessary.

10. Check the battery

electrolyte level if
accessible. Adjust as
necessary.

11. Check the battery posts,

cables, and charger for
loose connections,
corrosion, and proper
operation. Correct as
necessary.

12. Check the unit wiring for

loose connections,
corrosion, and damage.
Correct as necessary.

13. Check the engine

accessory drive belts for
wear, weather cracking,
and damage. Replace as
necessary.