Generac

®

Power Systems, Inc.

5

Figure 3 represents a single-phase, 3-wire generator AC
connection system. The stator assembly in this system
consists of a pair of stationary windings, with two leads
brought out of each winding. Each single winding can
supply 120 volts AC, 60 Hertz. When the two windings
are connected in series, a 240 volts, 60 Hertz AC output
results. Typically the two “hot” leads in the circuit are
Wires No. 11 and 44. The “Neutral” leads are the junc-
tion of Wires 22 and 33.

Figure 3 - Generator AC Connection System

MAIN CIRCUIT BREAKER

The generator’s main circuit breaker is included with the unit as
shipped from the factory. The breaker for each unit is described in
Figure 5 below.

GENERATOR FUEL SYSTEM

Your unit has been factory tested and adjusted using a
natural gas fuel system.

If propane (LP) gas is pre-

ferred, contact an authorized service dealer.

WARNING: Gaseous fuels such as natural and LP

(propane) gas are highly explosive. Even the slightest
spark can ignite such fuels and cause an explosion. No
leakage of fuel is permitted. Natural gas, which is lighter
than air, tends to collect in high areas. LP gas is heavier
than air and tends to settle in low areas.

ENGINE PROTECTIVE DEVICES

The engine has several safety switches which cause the
engine to automatically shut down under the following
conditions: low oil pressure, high coolant temperature,
engine overspeed, low coolant level or overcrank.

LOW OIL PRESSURE SWITCH:

This switch is normally-closed (N.C.) but is held open
by engine oil pressure during engine running. Should
operating oil pressure drop below about 8-10 psi (55-68
kPa), the switch contacts close and the engine shuts
down automatically (Figure 4).

Figure 4 - Low Oil Pressure Switch

Section 1 - General Information

Guardian Liquid-cooled 10 kW, 15 kW, 20 kW and 25 kW Generators

Model

Rating

Phase

Actual Current

C/B Rating*

% over rating

Circuit Breaker

004090-2

10,000

1

41.7

50

120%

50A BQ2

004091-2

10,000

3

30.1

40

133%

40A BQ3

004124-1

10,000

1

41.7

50

120%

50A BQ2

004125-1

10,000

3

30.1

40

133%

40A BQ3

004092-2

15,000

1

62.5

70

112%

70A BQ2

004093-2

15,000

3

45.2

60

133%

60A BQ3

004126-1

15,000

1

62.5

70

112%

70A BQ2

004127-1

15,000

3

45.2

60

133%

60A BQ3

004094-2

20,000

1

83.3

90

108%

90A BQ2

004095-2

20,000

3

60.2

70

116%

70A BQ3

004128-1

20,000

1

83.3

90

108%

90A BQ2

004096-2

25,000

1

104.2

125

120%

125A BQ2

004097-2

25,000

3

75.3

90

120%

90A BQ3

004130-1

25,000

1

104.2

125

120%

125A BQ2

004131-1

25,000

3

75.3

90

120%

90A BQ3

004474-0

25,000

1

104.2

125

120%

125A BQ2

004475-0

25,000

1

104.2

125

120%

125A BQ2

* Amp Rating of C/B structured under model.

Figure 5 - Main Circuit Breaker