Unpacking, Lifting the generator, Specifications – Generac 004090-2 User Manual

Page 9: Fuel consumption

Advertising
background image

Figure 8 - Control Module Assembly Circuit Board

OVERCRANK SHUTDOWN:

After 90 seconds of crank-rest cycles, this function ends
cranking if the engine fails to start in that 90-second
span.

DC FUSE

This clearly labeled fuse is located on the front panel of
the control system.

It protects the panel wiring and

components from damaging overload. Always remove
this fuse before commencing work on the generator.
The unit will not start or crank if the fuse is blown.
Replace the fuse with one of the same size, type, and rat-
ing.

Generac normally uses an AGC fuse rated at 30

amps.

UNPACKING

UNPACKING PRECAUTIONS:

Handle shipping cartons and crates with care. Use care
to avoid damage from dropping, bumping, collision, etc.
Store and unpack cartons with the proper side up, as
noted on the shipping carton.

INSPECTION:

After unpacking, carefully inspect the generator for any
damage that may have occurred during shipment. If
loss or damage is noted at the time of delivery, have the
person(s) making delivery note all damage on the freight
bill or affix his signature under the consignor’s memo of
loss or damage.

LIFTING THE GENERATOR

WARNING: When lifting or hoisting equipment is used,

be careful not to touch overhead power lines. The
generators weight of more than 900 pounds requires
proper tools, equipment, and qualified personnel to be
used in all phases of handling and unpacking.

SPECIFICATIONS

ENGINE SPECIFICATIONS

Make................................................................................Mitsubishi
Displacement ................................................92 inches

3

(1.5 liters)

Cylinder Arrangement........................................................4, in-line
Valve Arrangement..................................................Overhead Cam
Firing Order..........................................................................1-3-4-2
Number of Main Bearings ............................................................5
Compression Ratio ................................................................9 to 1
No. of Teeth on Flywheel ..........................................................104
Ignition Timing

at 1800 rpm ....................................................35 degrees BTDC
at 3600 rpm ....................................................43 degrees BTDC

Spark Plug Gap ....................................................0.020-0.025 inch
Recommended Spark Plugs

Champion ......................................................................RN11YC4

Oil Pressure......................................................................30-50 psi
Crankcase Oil Capacity..........................4.0 U.S. quarts (3.8 liters)
Recommended Engine Oil..........................................SAE 15W-40
Type of Cooling System ....................Pressurized, closed recovery
Cooling Fan ................................................................Pusher Type
Cooling System Capacity ........................2 U.S. gallons (7.6 liters)
Recommended Coolant..............................Use a 50-50 mixture of

ethylene glycol base.

FUEL CONSUMPTION

Models 004096, 004097, 004130, 004131, 004474, 004475

Using Natural Gas ....................................441 cu. ft. per hour
Using LP Gas ........................175 cubic ft.(4.8 gal.) per hour

Models 004094, 004095, 004128

Using Natural Gas ....................................359 cu. ft. per hour
Using LP Gas ........................143 cubic ft. (4.0 gal.) per hour

Model 004092, 004093, 004126, 004127

Using Natural Gas ....................................277 cu. ft. per hour
Using LP Gas ........................110 cubic ft.(3.1 gal.) per hour

Models 004090, 004091, 004124, 004125

Using Natural Gas ....................................195 cu. ft. per hour
Using LP Gas ..........................77 cubic ft. (2.2 gal.) per hour

NOTE:

Fuel consumption is given at rated maximum con-

tinuous power output when using natural gas rated

at 1000 Btu per cubic foot; or LP gas rated 2520

Btu per cubic foot. Actual fuel consumption

obtained may vary depending on such variables as

applied load, ambient temperature, engine condi-

tions and other environmental factors.

Section 1 — General Information

Guardian Liquid-cooled 10 kW, 15 kW, 20 kW and 25 kW Generators

Generac

®

Power Systems, Inc.

7