Commreq status word – GE GFK-2193A User Manual

Page 23

Advertising
background image


4-6

Series 90™-30 PROFIBUS Slave Module User's Manual – August 2004

GFK-2193A

4

COMMREQ Status Word

The following table defines the format of the Status Block used during the COMMREQ
handshake.

Status Word Format

Word Name

Description

1 State

(See “Status Word State
Codes” below.)

The state of the current COMMREQ request

2

LostCommand

Command code of the last command lost when
the CRL bit is set in Flags.

3 ErrorCode

Not

Used

4

AdditionalCode

Additional code for error reporting

Status Word State Codes

Value Description

0

Module has not yet processed the COMMREQ

1 Command

Complete

Note: This status does not necessarily mean success. Some commands have
reply data that must also be checked.

2

Command Terminated – module busy

3

Command Terminated – invalid command

4

Command Terminated – invalid command data

5

Command Terminated – not enough data

6

Command Terminated – command collision
An identical command, which has already reported completion, is currently being
processed and has not replied yet.

7

Command Terminated – not enough memory in reply area
The command did not specify sufficient PLC memory for the reply. Command will
be ignored.

8

Command Terminated – command-specific error. See ErrorCode and
AdditionalCode in the Status Block for more information.

9–255 Reserved

Advertising