Ic693pbs201 slave module specifications – GE GFK-2193A User Manual

Page 6

Advertising
background image


1-2

Series 90™-30 PROFIBUS Slave Module User's Manual – August 2004

GFK-2121A

1

SYS

COM

PROFIBUS DP

SLAVE

5-IGND

SERVICE RS232

PROFIBUS

3-TxD

2-RxD

5-IGND

8-A

3-B

1-SHLD

1

3

2

IC693PBS201

PROFIBUS

Slave Module

4

Key

1

LEDs

System (SYS) and Communications (COM)
indicators

2

Service Port

RS232, 9-pin male, D-Shell Connector. Used
for module firmware upgrades.

3

PROFIBUS
Port

9-pin female D-Shell Connector. Used for
connecting to a PROFIBUS network.

4

Label (not
shown)

Label on side of module contains catalog
number, description, standard conformance,
and serial number information

Figure 1-1. PROFIBUS Slave Module

IC693PBS201 Slave Module Specifications

Catalog number

IC693PBS201

Description

Series 90-30 Slave module for PROFIBUS DP networks

Configuration software
requirement

Requires Proficy Machine Edition Logic Developer version 2.6 or later

CPU version
requirement

Requires CPU firmware version 8.00 or later

Mounting location

Can reside in any Series 90-30 baseplate (CPU, expansion, or remote)
slot except for slot 1 of a modular CPU baseplate

Environment

Storage temperature = –40

°C to 85°C

Operating temperature = 0

°C to 60°C

Backplane current
consumption

450 mA at 5VDC (typical)

Data rates

Supports all standard Data Rates (9.6KBps, 19.2KBps, 93.75KBps,
187.5KBps, 500KBps, 1.5Mbps, 3MBps, 6MBps and 12MBps)

Status information

Slave Status Word
Firmware module revision

Note: The PROFIBUS Slave module does not support Sync and Freeze modes