(Word 9) Local PLC - Memory Starting Address: Word 9 determines the starting
address in the local PLC in which the response is to be written. The value entered is the
offset (0-based) from the beginning of PLC memory for the memory type and mode
specified in Word 8. This offset will be either in bits, bytes, or words depending on the
mode specified (for example, if Word 8=16 and Word 9=2, the starting address will be
%I9). Valid ranges of values depend on the PLC’s memory ranges.

(Word 10) Response Memory Size: Word 10 specifies the size of the memory block for
the response. The Response Memory Size is 25 words. If the Response Memory Size is
set smaller than 25, the COMMREQ will fail with a 7 in the COMMREQ Status Word. The
user is responsible for assuring that this area is large enough to contain the requested
data without overwriting other application data

Read Module Header Reply Data Format for Slave

Word Name

Description

Word 1

Command Code

Echo of the Command Code that this data block is replying to
(0x0005).

Word 2

ModuleType

Contains 1 if the module is a Slave and a 2 if the module is a
Master.

Word 3

PfbStatus

PROFIBUS Status register, also can be read using the Get
Device Status COMMREQ. For definitions, see page 4-8.

Word 4

ModuleVersion

Module firmware version.
0122h = 1.22

Word 5

ErrLanOffline

Counter. LAN went offline due to errors.

Word 6

DiagConf Total

confirmations.

Word 7

DiagInd Total

indications.

Word 8

ErrNotOk

Total not OK confirmations and indications.

Word 9

DiagSlaveUpdate

Number of updates the Slave has received from the Master

Word 10

ErrSlvErr

Count of Slave Configuration Errors

Word 11

ErrSlvTout

Count of Slave Watchdog timeouts (update not received in time)

Word 9

ErrInvReqLen

Invalid request length error counter.

Word 10

ErrFifo

FIFO overflow error counter.

Word 11

ErrRxOverun

Receive overrun error counter.

Word 12

ErrDblTok

Double token error counter.

Word 13

ErrRespErr

Response error counter.

Word 14

ErrSynErr

General network error counter.

Word 15

ErrNetTout

Network timeout error counter.

Word 16

ErrHsa

Station higher than HAS was heard counter.

Word 17

ErrStn

Duplicate station detected counter.

Word 18

ErrPasTok

Unable to pass token counter.

Word 19

ErrLasBad

Active station list is invalid.

Word 20

ErrInternal Internal

errors.

Word 21

ErrArg Argument

errors.

Word 22

ErrEventOverun

A new event occurred before the last one was cleared.

Note: If the Name starts with Err the value stops at the maximum. If the Name starts

with Diag the count rolls over to zero.