SAFE REFRIGERANT HANDLING

While these items will not cover every conceivable situation, they should serve as a useful guide.

IMPORTANT INFORMATION

The successful development of hermetically sealed refrigera-
tion compressors has completely sealed the compressor's
moving parts and electric motor inside a common housing,
minimizing refrigerant leaks and the hazards sometimes
associated with moving belts, pulleys or couplings.

Fundamental to the design of hermetic compressors is a
method whereby electrical current is transmitted to the
compressor motor through terminal conductors which pass
through the compressor housing wall. These terminals are
sealed in a dielectric material which insulates them from the
housing and maintains the pressure tight integrity of the
hermetic compressor. The terminals and their dielectric
embedment are strongly constructed, but are vulnerable to
careless compressor installation or maintenance proce-
dures and equally vulnerable to internal electrical short
circuits caused by excessive system contaminants.

In either of these instances, an electrical short between the
terminal and the compressor housing may result in the loss
of integrity between the terminal and its dielectric embed-
ment. This loss may cause the terminals to be expelled,
thereby venting the vaporous and liquid contents of the
compressor housing and system.

A venting compressor terminal normally presents no danger
to anyone, providing the terminal protective cover is properly
in place.

If, however, the terminal protective cover is not properly in
place, a venting terminal may discharge a combination of

(a) hot lubricating oil and refrigerant

(b) flammable mixture (if system is contaminated

with air)

in a stream of spray which may be dangerous to anyone in the
vicinity. Death or serious bodily injury could occur.

Under no circumstances is a hermetic compressor to be
electrically energized and/or operated without having the
terminal protective cover properly in place.

See Service Section S-17 for proper servicing.

WARNING

R

EFRIGERANTS ARE HEAVIER THAN AIR.

T

HEY CAN "PUSH OUT" THE

OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE.

T

O AVOID

POSSIBLE DIFFICULTY IN BREATHING OR DEATH:

N

EVER PURGE REFRIGERANT INTO AN ENCLOSED ROOM OR SPACE.

B

Y

LAW, ALL REFRIGERANTS MUST BE RECLAIMED.

I

F AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTILATE THE AREA

BEFORE BEGINNING WORK.

L

IQUID REFRIGERANT CAN BE VERY COLD.

T

O AVOID POSSIBLE FROST-

BITE OR BLINDNESS, AVOID CONTACT WITH REFRIGERANT AND WEAR

GLOVES AND GOGGLES.

I

F LIQUID REFRIGERANT DOES CONTACT YOUR

SKIN OR EYES, SEEK MEDICAL HELP IMMEDIATELY.

A

LWAYS FOLLOW

EPA

REGULATIONS.

N

EVER BURN REFRIGERANT,

AS POISONOUS GAS WILL BE PRODUCED.

WARNING

S

YSTEM CONTAMINANTS, IMPROPER SERVICE PROCEDURE AND/OR PHYSICAL

ABUSE AFFECTING HERMETIC COMPRESSOR ELECTRICAL TERMINALS MAY

CAUSE DANGEROUS SYSTEM VENTING.

WARNING

T

O AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE

HANDLING OF REFRIGERANTS.

WARNING

T

O AVOID POSSIBLE EXPLOSION, USE ONLY RETURNABLE (NOT DISPOSABLE)

SERVICE CYLINDERS WHEN REMOVING REFRIGERANT FROM A SYSTEM.

E

NSURE THE CYLINDER IS FREE OF DAMAGE WHICH COULD LEAD TO A

LEAK OR EXPLOSION.

E

NSURE THE HYDROSTATIC TEST DATE DOES NOT EXCEED 5 YEARS.

E

NSURE THE PRESSURE RATING MEETS OR EXCEEDS 400 LBS.

W

HEN IN DOUBT, DO NOT USE CYLINDER.

WARNING

T

O AVOID POSSIBLE EXPLOSION:

N

EVER APPLY FLAME OR STEAM TO A REFRIGERANT CYLINDER.

I

F YOU

MUST HEAT A CYLINDER FOR FASTER CHARGING, PARTIALLY IMMERSE

IT IN WARM WATER.

N

EVER FILL A CYLINDER MORE THAN 80% FULL OF LIQUID REFRIGERANT.

N

EVER ADD ANYTHING OTHER THAN

R

-22 TO AN

R

-22 CYLINDER OR

R

-410

A

TO AN

R

-410

A

CYLINDER.

T

HE SERVICE EQUIPMENT USED MUST

BE LISTED OR CERTIFIED FOR THE TYPE OF REFRIGERANT USED.

S

TORE CYLINDERS IN A COOL, DRY PLACE.

N

EVER USE A CYLINDER

AS A PLATFORM OR A ROLLER.

WARNING

T

HE

U

NITED

S

TATES

E

NVIRONMENTAL

P

ROTECTION

A

GENCY ("

EPA

")

HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND

DISPOSAL OF REFRIGERANTS INTRODUCED INTO THIS UNIT.

F

AILURE TO

FOLLOW THESE REGULATIONS MAY HARM THE ENVIRONMENT AND CAN

LEAD TO THEH IMPOSITION OF SUBSTANTIAL FINES.

T

HESE REGULATIONS

MAY VARY BY JURISDICTION.

S

HOULD QUESTIONS ARISE, CONTACT YOUR

LOCAL

EPA

OFFICE.