Servicing, Warning, S-61a checking heater limit control(s) – Goodmans ASX User Manual

Page 59

Advertising
background image

SERVICING

59

Alternately, the system CFM can be determined by operating
the electric heaters and indoor blower WITHOUT having the
compressor in operation. Measure the temperature rise as
close to the blower inlet and outlet as possible.

If other than a 240V power supply is used, refer to the BTUH
CAPACITY CORRECTION FACTOR
chart below.

BTUH CAPACITY CORRECTION FACTOR

SUPPLY VOLTAGE

250

230

220

208

MULTIPLICATION FACTOR

1.08

.92

.84

.75

EXAMPLE: Five (5) heaters provide 24.0 KW at the rated
240V. Our actual measured voltage is 220V, and our
measured temperature rise is 42°F. Find the actual CFM:

Answer: 24.0KW, 42°F Rise, 240 V = 1800 CFM from the
TEMPERATURE RISE chart on the right.

Heating output at 220 V = 24.0KW x 3.413 x .84 = 68.8
MBH.

Actual CFM = 1800 x .84 Corr. Factor = 1400 CFM.

NOTE: The temperature rise table is for sea level installa-
tions. The temperature rise at a particular KW and CFM will
be greater at high altitudes, while the external static pressure
at a particular CFM will be less.

TEMPERATURE RISE (F°) @ 240V

CFM

4.8

KW

7.2

KW

9.6

KW

14.4

KW

19.2

KW

24.0

KW

28.8

KW

600

25

38

51

-

-

-

-

700

22

33

43

-

-

-

-

800

19

29

38

57

-

-

-

900

17

26

34

51

-

-

-

1000

15

23

30

46

-

-

-

1100

14

21

27

41

55

-

-

1200

13

19

25

38

50

-

-

1300

12

18

23

35

46

-

-

1400

11

16

22

32

43

54

65

1500

10

15

20

30

40

50

60

1600

9

14

19

28

38

47

57

1700

9

14

18

27

36

44

53

1800

8

13

17

25

34

42

50

1900

8

12

16

24

32

40

48

2000

8

12

15

23

30

38

45

2100

7

11

14

22

29

36

43

2200

7

11

14

21

27

34

41

2300

7

10

13

20

26

33

39

HTR

KW

3.0

KW

4.7

KW

6.0

KW

7.0

KW

9.5

KW

14.2

KW

19.5

KW

21.0

KW

BTUH 10200 16200 20400 23800 32400 48600 66500 71600

ELECTRIC HEATER CAPACITY BTUH

FORMULAS:
Heating Output = KW x 3413 x Corr. Factor

Actual CFM = CFM (from table) x Corr. Factor

BTUH = KW x 3413

BTUH = CFM x 1.08 x Temperature Rise (T)

CFM = KW x 3413

1.08 x T

T = BTUH
CFM x 1.08

S-61A CHECKING HEATER LIMIT CONTROL(S)

Each individual heater element is protected with a limit
control device connected in series with each element to
prevent overheating of components in case of low airflow.
This limit control will open its circuit at approximately 150°F.

HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.

1. Remove the wiring from the control terminals.

2. Using an ohmmeter, test for continuity across the nor-

mally closed contacts. No reading indicates the control
is open - replace if necessary.

IF FOUND OPEN - REPLACE - DO NOT WIRE AROUND.

S-61B CHECKING HEATER FUSE LINK

(OPTIONAL ELECTRIC HEATERS)

Each individual heater element is protected with a one time
fuse link which is connected in series with the element. The
fuse link will open at approximately 333°.

WARNING

Disconnect ALL power before servicing.

1. Remove heater element assembly so as to expose fuse

link.