SERVICING

46

S-16C CHECKING ECM MOTOR WINDINGS

HIGH VOLTAGE!
Disconnect ALL power before servicing
or installing. Multiple power sources
may be present. Failure to do so may
cause property damage, personal injury
or death.

1. Disconnect the 5-pin and the 16-pin connectors from the

ECM power head.

2. Remove the 2 screws securing the ECM power head and

separate it from the motor.

3. Disconnect the 3-pin motor connector from the power

head and lay it aside.

4. Using an ohmmeter, check the motor windings for con-

tinuity to ground (pins to motor shell). If the ohmmeter
indicates continuity to ground, the motor is defective and
must be replaced.

5. Using an ohmmeter, check the windings for continuity

(pin to pin). If no continuity is indicated, the thermal limit
(over load) device may be open. Allow motor to cool and
retest.

16-pin
connector

5-pin
connector

3-pin motor
connector

S-16D ECM CFM ADJUSTMENTS MBE / AEPF

MBE MOTOR

This section references the operation characteristics of the
MBE/AEPF models motor only. The ECM control board is
factory set with the dipswitch #4 in the “ON” position and all
other dipswitches are factory set in the “OFF” position. When
MBE/AEPF are used with 2-stage cooling units, dipswitch
#4 should be in the "OFF" position.

For most applications, the settings are to be changed
according to the electric heat size and the outdoor unit
selection.

The MBE/AEPF products use a General Electric ECM

TM

motor. This motor provides many features not available on
the traditional PSC motor. These features include:

Improved Efficiency

Constant CFM

Soft Start and Stop

Improved Humidity Control

MOTOR SPEED ADJUSTMENT

Each ECM™ blower motor has been preprogrammed for
operation at 4 distinct airflow levels when operating in
Cooling/Heat Pump mode or Electric Heat mode. These 4
distinct levels may also be adjusted slightly lower or higher
if desired. The adjustment between levels and the trim
adjustments are made by changing the dipswitch(s) either
to an "OFF" or "ON" position.

DIPSWITCH FUNCTIONS

The MBE / AEPF air handler motors have an electronic
control that contains an eight (8) position dip switch. The
function of these dipswitches are shown in Table 1.

D ipsw itch N um ber

Function

1
2
3

N /A

4

Indoor Therm ostat

5
6
7
8

C oo ling & H eat Pum p C FM

C FM Trim Adjust

Electric H eat

Table 1

CFM DELIVERY

Tables 2, 3, 5 and 6 show the CFM output for dipswitch
combinations 1-2, and 5-6.

Model

Switch 1

Switch 2

CFM

OFF

OFF

1,200

ON

OFF

1,000

OFF

ON

800

ON

ON

600

OFF

OFF

1,600

ON

OFF

1,400

OFF

ON

1,200

ON

ON

1,000

OFF

OFF

2,000

ON

OFF

1,800

OFF

ON

1,600

ON

ON

1,200

MBE1200

MBE1600

MBE2000

Electric Heat Operation

Table 2