0) instructions for pressure test gauge connection – Gas-Fired Products PTS Series 100 User Manual

Page 31

Advertising
background image

Form

#43343530

–30–

JJuly 08

14.0)

INSTRUCTIONS FOR PRESSURE TEST GAUGE CONNECTION

SIDE VIEW

43269050 Rev. A 03/08

DANGER

Failure to do so may result in death,

serious injury or property damage

FIRE HAZARD

This access panel must be closed

tightly with all the necessary screws

during operation.

Never operate the heater with the

access panel open or removed.

Failure to do so may result in death, serious injury or property

damage.

The access doors on either side of the burner must

be securely fastened before operating the heater.

The access panels must be closed tightly with all the necessary

screws during operation.

Never operate the heater with the access panel open or removed.

SUPPLY PRESSURE
1. The installer will provide a 1/8” N.P.T. tapped plug, accessible for test gauge connection immediately upstream

of the gas supply connection to the heater.


MANIFOLD PRESSURE– COMBINATION GAS VALVE IS FACTORY SET
Two-stage valves require that you check and adjust both high and low pressure regulator settings.

1. Turn the gas valve to the “OFF” position. Remove the 1/8” plug from the combination gas valve at the outlet

pressure tap and connect a 1/8” nipple to the tapped hole. Connect the gauge to the nipple. Turn on the gas
supply.

2. Set the heater to operate on high. With the main burner operating, check the full rate (high) burner manifold

pressure using a water manometer. Gauges that measure pressure in pounds per square inch are not accurate
enough to measure or set the manifold pressure. All measurements MUST BE made when this heater and all
other gas burning equipment that is connected to the gas supply system are operating at maximum capacity.

3. The combination gas valve is factory set and should not require adjustment. If high pressure adjustment is

required, remove the pressure regulator adjustment cap. Using a 3/32” hex Allen wrench, turn the inner
adjustment screw for HI pressure clockwise to increase or counterclockwise to decrease the gas pressure
to the burner.

4. After high pressure has been checked, check low pressure regulation.
5. Using a 3/32” hex Allen wrench, turn the inner adjustment screw for LO pressure clockwise to increase or
counterclockwise

to decrease the gas pressure to the burner.

6. Once high and low pressures have been checked and adjusted, replace pressure regulator adjustment cap.

Gas pressures are shown in the table below.








* Minimum permissible gas supply pressure for purpose of input adjustment.

GAS PRESSURE TABLE

SUPPLY PRESSURE

GAS TYPE

MANIFOLD PRESSURE

High Low

Minimum* Maximum

Natural Gas

3.5” W.C.

1.4” W.C.

5” W.C.

14” W.C.

Propane Gas

10.0” W.C.

4.0” W.C.

11” W.C.

14” W.C.

Advertising