MULTIPLE HEATER VENTING (CONNECTIONS INTO A COMMON VENT OR MANIFOLD)
Requirements for venting of multiple heaters are the same as described for SINGLE HEATER VENTING except as
follows:
1. The common vent size and total vent height is normally determined by the number of heaters per common

vent, length of horizontal connector runs, and connector rise. Connector lengths should be as short as
possible and have a minimum 1/2 inch per 20 foot fall. Without regard to connector rise and total vent
height due to many possible venting configurations, the following should be observed:

a. Common vent pipe & vent connector diameter should be no less than that shown in the following Vent

Sizing Table.

b. The connector length should be no more than 75% of the vertical portion of vent above the connector.

c. Where possible, use a Y-connector to the common vent.

2. Material for connectors should be constructed of galvanized sheet metal or other approved noncombustible

corrosion resistant material as allowed by state or local codes. All common vent pipe should be double wall,
Type B vent.

3. Avoid unnecessary bends. Limit to two (2) 90º elbows.
4. The entire length of vent connector shall be readily accessible for inspection, cleaning and replacement.
5. Groups of heaters with a common vent must be controlled by a common thermostat.

Multiple Heater Vertical venting arrangement.

Total

Vent

Height

Vent Cap (Leslie

VersaCap Type B)

Flashing

2” (5cm)

Clearance

Thimble

Seal Joint

and Annular

Space

10 ft (305cm)

or less

2 ft (77cm)

minimum

2 ft (77cm) minimum

(when no wall or

parapet exists)

4” Diameter

single wall Vent

W

all or

Parapet

See multiple

vent size table

for diameter

Flue Collar

adaptor

Connections to the common vent

must be arranged to avoid direct

opposition of exhaust products.

Plan View

Flue Adapter

Collar

#10 Self-Drill

Screws

(typical)

4” Vent Pipe

(horizontal position)

Vent Cap

(Breidert or

equivalent Type L)

2” (5cm)

Clearance

Thimble

1/2” (12mm) fall per 20 ft

(6m) toward vent terminal

6” (15cm)

minimum