6 stopping the generator, 7 applying loads to generator, 8 do not overload the generator – Generac 004700-0 User Manual

Page 11: 9 protection systems

Advertising
background image

Generac

®

Power Systems, Inc.

9

Section 2 – Operation

QUIETPACT 40G Recreational Vehicle Generator

2.6 STOPPING

THE

GENERATOR

1. Turn OFF all electrical loads using the means

provided (such as a main circuit breaker or
transfer switch).

2. Let generator run at no-load for a few minutes, to

stabilize internal engine generator temperatures.

3. Place the Start/Stop switch in its STOP position.

2.7 APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator,
observe these guidelines:

• Before applying electrical loads, let the generator

stabilize and warm up for a minute or two.

• DO NOT overload the generator.

2.7.1 LETTING THE ENGINE STABILIZE

The generator supplies correct rated voltage only at
the proper governed speed. Some electrical appli-
ances may be extremely sensitive to voltage. Incorrect
voltages can damage such appliances.

If electrical loads are applied at reduced operating
speeds, such loads imposed on the engine when suffi-
cient power is not available may shorten engine life.
Never turn ON electrical loads until after the generator
engine has started and stabilized at no-load.

2.8

DO NOT OVERLOAD THE
GENERATOR

You can read the rated wattage/amperage capacity of
your generator on the generator data decal (see
Section 1.1 on Page 4).

Applying electrical loads in excess of the unit’s rated
capacity will cause the engine/generator to automati-
cally shut down.

To avoid overloading, add up the wattage of all con-
nected electrical lighting, appliance, tool and motor
loads. This total should not be greater than the gen-
erator’s rated wattage capacity.

• Most lighting, appliance, tool and motor loads indi-

cate their required watts on their nameplate or
data plate. For light bulbs, simply note the wattage
rating of the bulb.

• If a load does not show its rated wattage, multiply

that load’s rated VOLTS times AMPS to obtain
WATTS.

• Induction type motors (such as those that run the

vehicle’s furnace fan, refrigerator, air conditioner,
etc.) need about 2-1/2 time more watts of power for
starting than for running (for a few seconds during
motor starting). Be sure to allow for this when con-
necting electrical loads to the generator. First, fig-
ure the watts needed to start electric motors in the
system. To that figure, add the running wattages of
other items that will be operated by the generator.

• Do not apply heavy electrical loads for the first two

or three hours of operation.

2.9 PROTECTION

SYSTEMS

2.9.1 LOW OIL PRESSURE SWITCH

This switch (Figure 2.2) has normally closed (N.C.)
contacts that are held open by engine oil pressure dur-
ing cranking and operating. Should oil pressure drop
below a preset level, switch contacts close, and the
engine automatically shuts down. The unit should not
be restarted until oil is added.

2.9.2 HIGH TEMPERATURE SWITCH

This switch (Figure 2.2), which has normally open
(N.O.) contacts, is mounted near the oil filter. The
contacts close if the temperature should exceed
approximately 293º F (145º C), initiating an engine
shutdown.

Figure 2.2 – Low Oil Pressure and

High Temperature Switches

High Temperature Switch

Low Oil Pressure
Switch

Advertising