15.0) ELECTRICAL

CONNECTIONS

Failure to do so may result in death or serious injury.

This appliance must be connected to a properly grounded electrical source.

Disconnect electrical power and gas supply before servicing.

ELECTRIC SHOCK HAZARD

1. All electric wiring shall conform to the latest edition of the National Electrical Code (ANSI/NFPA No. 70), or

the code legally authorized in the locality where the installation is made.

2. The unit must be electrically grounded in accordance with the National Electrical Code (ANSI/NFPA No.

70-latest edition). In Canada, refer to current standard C22.1 Canadian Electrical Code Part 1.

3. The wiring providing power to the heater shall be connected to a permanently live electrical circuit, one that

is not controlled by a light switch.

4. The power supply to the unit should be protected with a fused disconnect switch or circuit breaker. A service

switch, as required by local codes, shall be located in the vicinity of the heater (check local codes for
allowable distances) and should be identified as Heater Service Switch. All electrical wiring must be located
in accordance with the required Clearances to Combustibles below the heater as listed on the nameplate on
the heater.

5. Connection to the power supply is provided by a 18/3 gauge x 72” long cord with grounded 3 prong plug.
6. The post purge function of the burner (fan on for 30 seconds after the call for heat) will only be enabled

when using a 24 Volt thermostat. With the line Voltage thermostat post purge operation is disabled.

Optional 24V thermostat connection

Jumper wire with 1/4” terminals pre-

installed. Remove the jumper and use

these two terminals for the 24V

thermostat connection if required.

72” grounded 3 prong

electrical cord

Liquid tight fitting

must be tight to

prevent ingress of

moisture in harsh

environments.

Pressure Regulator Adjustment

(under cap screw)

1/8” NPT

Inlet Pressure

Tap with 3/16” Hex

Allen Wrench Plug

1/8”NPT

Outlet Pressure

Tap with 3/16” Hex

Allen Wrench Plug

Gas Control

Knob

Wiring

Terminals (2)

Ground

Terminals (2)

OUTLET

INLET

CAUTION

Never jumper these terminals. This

shorts out valve coil and may burn

out heat anticipator in thermostat.

STEP-OPENING

GAS CONTROL VALVE

ON

OFF

MV