IGNITION MODULE DIAGNOSTICS

Flame Fault

If at any time the main valve fails to close completely and maintains a flame, the full time flame sense circuit will
detect it and energize the combustion blower. Should the main valve later close completely removing the flame
signal, the combustion blower will power off following the post purge period.

Fault Conditions

The LED located on the ignition module will flash ON
for ¼ second, then OFF for ¼ second during a fault
condition. The pause between fault codes is 3
seconds.























24.0) INSTALLATION

DATA

Date of Installation:

# of Heaters in System:

Serial No.

Model: PTS or PTU

N = Natural Gas
L = Propane Gas


Error Mode

LED Indication

Internal Control Failure

Steady On

Air Flow Fault

1 Flash

Gas valve failure (stuck open) 2 Flashes
Ignition Lockout

3 Flashes

MULTIPURPOSE METER

USE

MICROAMP

SCALE

BLACK (-)

RED (+)

LED Display

GND

V2

FC-

FC+

V1

(W)TH

Ignition Module (Fenwal)

Flame Sensor Current Check

(R) 24VAC

L1
IND
NC

P.SW

S1