Operation, Voltage-thresholds tab sensitivity tab – MGE UPS Systems 3000 User Manual

Page 19

Advertising
background image

3400723100/AD

- Page 19

3. Operation

Configurable function

Output voltage on battery power

Upper threshold for transfer to battery power

Fader-mode cut-in threshold

Booster-mode cut-in threshold

Lower threshold for transfer to battery power

Maximum input-voltage range

Default setting

120 V

151 V

132 V

102 V

89 V

Disabled

Options

100 V - 127 V

141 V to 153 V

127 V to 138 V

92 V to 108 V

80 V to 94 V

Enabled

Configurable function

UPS sensitivity level

Default setting

Normal

Options

High or low

Voltage-thresholds tab

Sensitivity tab

NOTE: For more information about these settings, refer to the Help function of the "UPS Driver" software.

(1) Lower threshold for transfer to battery mode = 70 V