SECTION 7 − OPERATING AUXILIARY EQUIPMENT

.

Generator power decreases as weld

current increases. Set Weld Output

control to maximum for full generator

power output at AC receptacles.

1

240 V AC Receptacle RC1

RC1 supplies 60 Hz single-phase power at

weld/power speed. Maximum output is 6

kVA/kW (peak) or 5.5 kVA/kW (continu-

ous).
2

120 V 20 A AC Duplex Receptacle

RC2

3

120 V 20 A AC Duplex Receptacle

RC3

RC2 and RC3 supply 60 Hz single-phase

power at weld/power speed. Maximum

output from RC2 or RC3 is 2.4 kVA/kW.
NOTICE − Do not parallel the two 120V du-

plex receptacles.
4

Supplementary Protector CB1

CB1 protects the receptacles from over-

load. If CB1 opens, the receptacles do not

work. Move switch to the On position to re-

set.
5

Supplementary Protectors CB2, CB3

CB2 protects RC2 and CB3 protects RC3

from overload. If the supplementary pro-

tector opens, the receptacle does not

work. Press button to reset.

.

If supplementary protector continues
to open, contact Factory Authorized

Service Agent.

Combined output of all receptacles limited

to 5.5 kVA/kW continuous rating of the

generator (See Section 12 − Generator

Power Guidelines).

EXAMPLE: If 10 A is drawn from each 120

volt duplex receptacle, only 13 A is avail-

able from the 240 V receptacle.

2 x (120 V x 10 A) + (240 V x 13 A) = 5.5

kVA/KW.

7-1. Generator Power Panel Receptacles

218 611−B

1

2

4

3

5

If unit does not have GFCI recep-

tacles, use GFCI-protected exten-

sion cord.