Specifications, Circuit Breakers and Powerflow Diagrams

1.4.1

Circuit Breakers

EPS 8000 UPS circuit breakers (except the battery disconnect circuit breaker QF1) are located behind the doors of

the Input/Output cabinet. Following is a brief description of the available circuit breakers and contacts, and their

function (Figures 1-2, 1-3, and 1-4).

Q1

Input isolation circuit breaker, used to isolate the UPS from the main AC input (mains 1) and provide

input current protection.

QF1

Battery disconnect circuit breaker, external to the UPS, used to disconnect the battery from the UPS.

QF1 provides isolation and protection between the UPS and its battery system.

Q3BP

(optional) Maintenance bypass circuit breaker, used to supply the attached load via the bypass source

while the UPS is being serviced.

Q5N

Optional UPS isolation circuit breaker, used to isolate the UPS module from the attached load.

Q4S

Bypass input circuit breaker; it is used to isolate the UPS from the bypass input (mains 2) source and

provide back-feed protection. This circuit breaker is mounted inside the Input/Output cabinet for 625

and 555 kVA units.

Figure 1-2: Circuit Breaker Locations on the EPS 8000. (Q4S not shown)

I N P U T
C B, Q 1