Drawing 1a, Piping, Fig. 5-3 – Munchkin HIGH EFFICIENCY HEATER with the "925" Controller User Manual

Page 26

Advertising
background image

26

PIPING

Standard Munchkin boiler
Retrofit piping (zoning with valves)

Space heating mode

Munchkin boiler

P1

Super Stor

indirect DHW tank

T/P

Drawing 1A

make-up water

zone valves

purging

valves

NOTES:

1.

This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.

2.

Adjust flow bypass valve for the following minimum boiler flow rates in any operating mode:
Munchkin model T50M: 3 gpm
Munchkin model T80M: 3 gpm
Munchkin model 80M: 3 gpm
Munchkin model 140M: 5 gpm
Munchkin model 199M: 7 gpm

3.

The minimum pipe size for connecting a Super Stor water heater is 1 inch.

4.

The minimum pipe size for connecting a Munchkin boiler is 1.25 inches.

5.

All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.

6.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

7.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

8.

A purging valve may be used in lieu of the ball valve / hose bib combination shown

.

V1

flow

bypass

valve

anti-scald

mixing valve

cold

water

OFF

Fig. 5-3

NOTE: FOR VISION PIPING APPLICATIONS, REFER TO THE VISION INSTALLATION PIPING DIAGRAMS.

Advertising