29

PIPING

Standard Munchkin boiler
Preferred piping (zoning with valves)

Domestic water heating mode

Munchkin boiler

P1

Super Stor

indirect DHW tank

T/P

Drawing 2B

make-up water

V1

zone valves

anti-scald

mixing valve

purging

valves

closely

spaced

tees

differential
pressure
bypass
valve

P2

NOTES:

1.

This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.

2.

Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure
drop operates by itself.

3.

The minimum pipe size for connecting a Super Stor water heater is 1 inch.

4.

The minimum pipe size for connecting a Munchkin boiler is 1.25 inches.

5.

All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.

6.

The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.

7.

Install a minimum of 12 diameters of straight pipe upstream of all circulators.

8.

A purging valve may be used in lieu of the ball valve / hose bib combination shown.

9.

A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream
of all closely spaced tees.

cold

water

OFF

OFF

OFF

OFF

Fig. 5-6

NOTE: FOR VISION PIPING APPLICATIONS, REFER TO THE VISION INSTALLATION PIPING DIAGRAMS.