MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 11

Advertising
background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-5

1.3 Overview

The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered from the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static
bypass line.

A) Normal

operation:

Load power supplied by each system UPS inverter.


Figure 1.1 Single Line Diagram - Normal Operation: Load powered by UPS inverters










During normal operation, the path through the UPS inverters is used to power the load.

Referring to Figure 1.1: For each system UPS, the Input AC power is converted to DC by
the Rectifier. DC power is utilized to charge the UPS battery and to provide power to the
Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations
existing in the input power before it reaches the critical load.

The power drawn by the critical load is equally shared between all system UPS.

In the event of a UPS module failure, the critical load power will be continually supplied
and shared by all other system UPS.

In the event of a load overcurrent, all system UPS will transfer to bypass without
interruption to the critical load.

CB1

Static Transfer

Switch

AC Bypass

Input

AC input

CB

CB3

52S

52C

User supplied
MCCB

UPS Module

Battery cabinet

CB2

Power Flow

Not in Use

RECTIFIER

INVERTER

Output