MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 33

Advertising
background image


MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

2-12

Terminals 7 to 8

"Power Demand Command" contact input (IN4)

This contact is used to control the input power. Power demand is turned ON
when the contact is closed, and power demand is turned OFF when the
contact is open.

Terminals 9 to 18 "Spare" contact input (IN5 through IN9)
Terminals 19 to 20 "Remote EPO" contact input

Used to perform a remote UPS Emergency Power Off (EPO).
The load will be dropped.

NOTE:

The UPS is equipped with a selectable output contact item. The above

items are the default settings. Contact MITSUBISHI ELECTRIC
AUTOMATION, INC. for setup information

.

NOTE :

In all cases, a switch having a protective cover is recommended in

order to reduce the possibility of accidental operation

.

2.5 External communication connector

This is an RS232C port for “DiamondLink”* monitoring software.
The layout of connector is shown in Figure 2.18.

FIGURE 2.18 External communication connector (NEC Class2)

Pin 1.

: Not used

Pin 2. RXD

: Receive data

Pin 3. TXD

: Transmit data

Pin 4.

: Not used

Pin 5. GND

: Signal ground

Pin 6.

: Not used

Pin 7.

: Not used

Pin 8.

: Not used

Pin 9.

: Not used

* Consult MITSUBISHI ELECTRIC AUTOMATION, INC. for details on

DiamondLink

monitoring software and its capabilities.

D-SUB 9Pin (male)

PCB IOAU-04

1
2
3
4
5

6
7
8
9

Advertising