MITSUBISHI ELECTRIC 9800A SERIES UPS systems User Manual

Page 19

Advertising
background image



MITSUBISHI ELECTRIC 9800A SERIES UPS

MITSUBISHI
ELECTRIC

9800A SERIES UPS

OWNERS / TECHNICAL MANUAL

Page Number:

1-13

1.4 Specifications

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The
name plate is located on the inside of the UPS front door.

TABLE 1.1 Power Specifications

Rated output

Power

Input voltage

3 phase / 3 wire

Bypass input voltage

3 phase / 4 wire

Output voltage

3 phase / 3 or 4 wire

100kVA / 80kW

150kVA / 120kW
225kVA / 180kW
300kVA / 270kW
375kVA / 338kW
500kVA / 450kW
750kVA / 675kW

480V
480V
480V
480V
480V
480V
480V

480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V

480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V
480V or 600V

TABLE 1.2 UPS Module Information

UPS

[kVA]

CABLE

ENTRY

WIDTH

[in / mm]

DEPTH

[in / mm]

HEIGHT

[in / mm]

WEIGHT

[lb./ kg]

HEATING

[kBTU/h]

100

BOTTOM

43.3 / 1100

29.8 / 758

79.7 / 2025

2100 / 950

22.0

150

BOTTOM

47.2 / 1200

29.8 / 758

79.7 / 2025

2820 / 1275

33.0

225

BOTTOM

55.1 / 1400

29.8 / 758

79.7 / 2025

3310 / 1500

45.0

300

TOP

76.8 / 1950

37.7 / 958

79.7 / 2025

4990 / 2260

68.0

375

TOP

76.8 / 1950

37.7 / 958

79.7 / 2025

5250 / 2380

84.0

500

TOP

114.2 / 2900

37.7 / 958

79.7 / 2025

6930 / 3140

98.0

750

TOP

129.9 / 3300

49.5 / 1258

79.7 / 2025

9655 / 4380

136.1

Advertising