Unit

Parts

Fan motor

Bearing

Fan belt

Air filter

Drain pan

Drain hose

Linear
expansion
valve
Heat
exchanger

Float switch

Display
lamp

Compres-
sor

Fan motor

Linear
expansion
valve
Heat
exchanger

Pressure
switch

Cooling fan
for inverter

Check frequency

6 months

3 months

6 months

1 year

6 months

1 year

6 months

1 year

Outdoors

(air-cooled)

Indoors

Checks

• Check operating noise.
• Measure insulation resistance.
• Check operating noise.

• Check belt tension.
• Visually check for wear and damage.
• Check operating noise.

• Visually check for contamination and

damage.

• Clean
• Check for contamination and blockage

of drain.

• Check for loose mounting screws.
• Check for deterioration.
• Check sealing of hose (inject water into

hose).

• Check for contamination and blockage

of drain.

• Check for deterioration.
• Check action using operation data.

• Check for blockage, contamination, and

damage.

• Check appearance.
• Check for adhesion of foreign matter.

• Check lighting of lamp.

• Check operating noise.
• Measure insulation resistance.
• Visually check for loose terminals.
• Check operating noise.
• Measure insulation resistance.
• Check action using operation data.

• Check for blockage, contamination, and

damage.

• Check for broken wiring, deterioration,

and unconnected connectors.

• Measure insulation resistance.
• Check operating noise.
• Measure insulation resistance.
• Check fault history.

Evaluation criteria

• No abnormal noises.
• Insulation resistance 1 M

Ω or more.

• No abnormal noises.

• Deflection load of 3 - 4kg per belt. Opti-

mum deflection of 5mm.

• Maximum stretch in belt circumference

of 2% in comparison to initial circumfer-
ence.

• No wear or damage.
• No abnormal noises.
• No contamination or damage.

• No contamination or blockage.
• No loose screws.
• No significant deterioration.

• No contamination or blockage.
• No significant deterioration.

• Appropriate temperature change in re-

lation to change in control opening.

• No blockage, contamination or damage.

• No deterioration or broken wiring.
• No foreign matter.

• Lit at output ON.

• No abnormal noises.
• Insulation resistance 1 M

Ω or more.

• No loose terminals.
• No abnormal noises.
• Insulation resistance 1 M

Ω or more.

• Appropriate temperature change in re-

lation to change in control opening.

• No blockage, contamination or damage.

• No broken wiring, deterioration, or un-

connected connectors.

• Insulation resistance 1 M

Ω or more.

• No abnormal noises.
• Insulation resistance 1 M

Ω or more.

• No heat-sink heating protection (4230,

4330) in fault history.

Maintenance

Replace if insulation has deteriorated.

Replace if abnormal noises continue de-
spite replenishing oil.
Replenish oil annually.
Adjust tension.
Replace if stretch in belt circumference
is 2% or more, or if belt has been in use
for 8000 hours or more.
Replace if belt is worn or damaged.

Clean
Replace if filter is significantly contami-
nated or damaged.
Clean if contaminated or blocked.
Tighten screws.
Replace if deterioration is significant.

Clean if contaminated or blocked.
Replace if deterioration is significant.

Replace if the valve itself is the cause of
problems in operation.

Clean

Replace if wiring is broken or deteriora-
tion is significant.
Clean if foreign matter present.
Replace lamp if not lit at output ON.

Replace if insulation has deteriorated
while coolant has been circulating.
Tighten terminals if loose.
Replace if insulation has deteriorated.

Replace if the valve itself is the cause of
problems in operation.

Clean

Replace if wiring is broken, shorted, or
has significantly deteriorated, or if insu-
lation has deteriorated.
Replace in case of abnormal noises, if
insulation has deteriorated, or if a fault
has occurred.

15. Periodic Checks