16. Specifications

Notes: *1 Cooling capacity indicates the maximum value at operation under the following condition.

Cooling: Indoor: 27

°C DB/19 °C WB

Outdoor: 35

°C DB

*2 The operating noise is the data that was obtained in an anechoic room.

Both indoor and outdoor temperatures assume a relative humidity of 30 - 80%.

Contact your retailer if the unit is to be used at an outdoor dry bulb temperature of –5

°C or lower.

Power source
Cooling capacity*1

kW

Height

mm

Dimension

Width

mm

Depth

mm

Net weight

kg

Fan

Airflow rate (Low-Middle-High)

m

3

/min

Noise level*2

dB(A)

Filter

PFD-P250VM-A

28

1200

350
160

59

Item

Model

PFD-P·VM-A series

Dry bulb temperature
Wet bulb temperature

Indoor

12

°C~24 °C

Outdoor

–5

°C~43 °C

17. Warranty and Servicing

s

s

s

s

s In addition to daily checks (eg cleaning of filters), periodic maintenance and checks by a skilled technician are required to ensure that the unit is maintained

in a good condition for a long period of time, and that it may be used with confidence.

Check Frequency for the standard maintenance and checks, and the Maintenance Frequency associated with periodic checks are as follows.

<Maintenance and Check Frequencies>
1. Preventative Maintenance Guidelines

The following maintenance frequencies are a guide to the replacement of parts as based on the results of periodic checks and scheduled frequency of repairs. They do
not imply that replacement is always necessary in accordance with the maintenance frequency (except for consumables such as fan belts).
Note that the following does not indicate maintenance periods.

Table 2 Maintenance and Check Frequencies

2. Cautions

The maintenance and check frequencies in the table above are applicable under the following conditions of use.
A. Normal conditions of use, with infrequent starting and stopping (varies with model, however interval of starting and stopping would normally use is generally six times

or less per hour).

B. 24 hours using.

The maintenance interval may need to be reduced under any of the following conditions.
1 Use under conditions of high temperature or humidity, or in locations in which variations in temperature and humidity are considerable.
2 Use in locations in which power supply variations (e.g. voltage, frequency, waveform distortion) are considerable. Note that the unit cannot be used outside the

allowable range of conditions.

3 Use in locations subject to considerable vibration and shock.
4 Use in an atmosphere containing toxic gases (e.g. dust, salt, sulfuric acid vapor, hydrogen sulfide) or oil mist etc.

Unexpected events may occur even when periodic checks are implemented based on the check frequency. In such cases the appropriate repairs outside the period of
the warranty are chargeable.

Unit

Parts

Fan motor
Bearing
Fan belt
Air filter
Drain pan
Drain hose
Linear expansion valve
Heat exchanger
Float switch
Display lamp
Compressor
Fan motor
Linear expansion valve
Heat exchanger
Pressure switch
Inverter cooling fan

Check frequency

6 months

3 months

6 months

1 year

6 months

1 year

6 months

1 year

Outdoors

(air-cooled)

Indoors

Maintenance frequency

40,000 hours
40,000 hours

8,000 hours

5 years
8 years
8 years

25,000 hours

5 years

25,000 hours

8,000 hours

40,000 hours
40,000 hours
25,000 hours

5 years

25,000 hours
40,000 hours

Ordinarily check

Maintenance check


Remarks

Replenish oil annually.
Consumable part
Check interval are affected by local conditions.

PFD-P500VM-A

56

1800

480
320

64

3N~/380-415V (50Hz), 400-415V (60Hz)

1895

800

Long life filter