NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

A = Clearance above grade, veranda, porch, deck, or balcony (min.

12”/30cm)

B = Clearance to window or door that may be opened (min. 12”/30cm

above - 48”/1.2m below and to the side)

C = Clearance to permanently closed window *(min. 12”/30cm)
D = Vertical clearance to ventilated soffit located above the terminal

within a horizontal distance of *(min. 24”/60cm) from the center-
line of the terminal (min. 22”/55cm) check with local code.

E = Clearance to unventilated soffit *(min. 12”/30cm)
F = Clearance to outside corner *(min. 12”/30cm)
G = Clearance to inside corner *(min. 12”/30cm)
H = Not to be installed above a meter/regulator assembly within *(min.

36”/90cm) horizontally from the centerline of the regulator.

J = Clearance to service regulator vent outlet *(min. 72”/1.8m)
K = Clearance to non-mechanical air supply inlet to building or the

combustion air inlet to any other appliance *(min. 48”/1.2m)

L = Clearance to a mechanical air supply inlet *(min. 120”/3.1m)
M = **Clearance above paved sidewalk or a paved driveway located on

public property *(min. 84”/2.1m)

N = ***Clearance under veranda, porch, deck, or balcony (min.

12”/30cm)

Note:
*

Local codes or regulations may require different clearances.

** A vent shall not terminate directly above a sidewalk or paved

driveway which is located between two single family dwellings
and serves both dwellings.

*** Only permitted if veranda, porch, deck, or balcony is fully open on

a minimum of two sides beneath the floor.

Vent Terminal
Area Where Terminal Is Not Permitted

(From Eave)

Vertical Terminal

Vertical Terminal

Fixed Closed

Able To Open

A

A

B

B

B

B

C

D

E

F

G

H

J

K

L

M

N

24”

(610mm)

B

Air Supply Inlet

24”

(610mm)

Figure 9

Vent Termination Locations