Maintenance, 1 trouble-shooting – MGE UPS Systems 2200 User Manual

Page 20

Advertising
background image

Page 20 -

34007115EN/AA

Troubleshooting requiring MGE UPS SYSTEMS after-sales support

4. Maintenance

4.1 Trouble-shooting

Indication

LED 17 goes ON and
the buzzer sounds
continuously.

Signification

UPS electronics have detected a UPS fault.

The connected equipment is no longer supplied.

The equipment connected to the UPS is no
longer protected.

Correction

Call the after-sales support
department.

Indication

LED 18 flashes and the
buzzer beeps once.

LED 17 flashes.

Signification

UPS overload. The power drawn by the connected
equipment exceeds UPS capacity.

A battery fault was detected during the automatic
battery test.

Correction

Check the power drawn by the
equipment and disconnect any non-
priority devices.

Replace the battery module (see
section 4.2).

Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (all versions)

Indication

The outlets are not
supplied with power even
though button 15 is ON.

Signification

One of the output-protection circuit breakers 7
on the rear panel is open.

Correction

Make sure there is not a short-

circuit on the outlets.

Clear the overload on the

concerned outlets by balancing the
equipment loads over the outlets.

Close the circuit breaker.

Troubleshooting not requiring MGE UPS SYSTEMS after-sales support (3000/3000 XL versions only)